See
Analogue input (AI)
,
View or configure sensor
for how to configure the
Sensor
curve.
4. If required, configure custom alarm(s).
•
See
Analogue input (AI)
,
Configure alarm(s)
for how to configure the alarm(s).
As you complete each configuration, write the settings to the controller.
7.9.3 Configure I/O name
To rename the input or output name:
1. Select
I/O name
I/O name
.
•
The
virtual keyboard
is displayed on screen to edit the I/O name.
•
2. Enter the required I/O name and select
Write
.
7.9.4 Configure function(s)
The functions available are organised in categories and groups, which are similar to a tree structure view.
For analogue inputs (AI) you can select either:
•
Analogue
: Analogue function(s)
•
Digital
: Supervised binary input function(s)
CAUTION
When using Supervised binary input function(s), you must configure the curve with y minimum 0 and y maximum 1 before
selecting the binary function(s).
OPERATOR'S MANUAL 4189341099G UK
Page 63 of 130