Method
1. If possible, make sure that there is enough power available for the system. That is, are there enough
gensets running to supply the system?
2. Use the
Switchboard control
switch (on the switchboard) to change the controller to SWBD control.
3. Depending on the problem you can use the switchboard to do the following actions. If you cannot do these
actions during switchboard control, the controller will not be able to do them either. You will have to
continue troubleshooting to find the source of the problem.
a. Start the genset.
b. Use the GOV up and GOV down inputs to control the frequency from the genset.
c. Do a manual synchronisation and close the breaker.
d. Manually regulate the load to de-load the breaker, and then open the breaker.
e. Stop the genset.
More information
See
Troubleshooting
, in the
Commissioning guidelines
for troubleshooting regulators and terminal damage.
INFO
This method can be adapted to troubleshoot any controller analogue output.
13.3 Troubleshooting alarms
13.3.1 Troubleshooting alarms
The system has many pre-configured and configurable alarm protections. Activated alarms require action to resolve the problem in
the system. An active alarm has an active alarm protection, which is designed to protect the system and equipment.
More information
See
Alarms
for more information about how alarms can be handled.
13.4 Network and communication
13.4.1 DEIF network redundancy broken
Alarm
DEIF network redundancy broken
Configuration
Configure > Parameters > Communication > DEIF network
Possible cause(s)
•
System never had a redundant DEIF network connection.
•
The existing redundant DEIF network connection has become unplugged, damaged or faulty.
Checks and
recovery
•
For a system with no redundant DEIF network connection configured, you can either:
◦
Install a redundant DEIF network connection.
◦
See
Wiring the communication
in the
Installation instructions
for more information about
installing the Ethernet communication.
◦
Alternatively, disable the DEIF network redundancy alarm:
◦
Set the alarm to
Not enabled
by configuring the parameter:
◦
Configure > Parameters > Communication > DEIF network > DEIF network redundancy
broken
•
For a system with a redundant DEIF network connection already configured:
◦
Check the Ethernet cabling has not been accidentally damaged or unplugged.
OPERATOR'S MANUAL 4189341099G UK