Programming manual MPC-1
4189340103E
Power controller
Pset1 = F0100kW
Setpoint 1 (kW) for constant
power transfer to/from mains(B
indicates "Consumption from ma-
ins", L indicates "Delivery to main-
s", F indicates fixed generator
power). Active setpoint, when
"auto 1" (terminal 3) is connected
to + 24 VDC.
Power controller
Psetp.2 = F0200kW
Setpoint 2 (kW) for constant
power transfer to/from mains.
Active setpoint, when "auto 2" (ter-
minal 5) is connected to + 24
VDC. NOTE: If "Setpoint extern" =
ON (see paragraph 1.8.4), the set-
point 2 input controls the "auto"
function only. The actual setpoint
is determined via a 4(0)...20 mA
transmitter.
NOTE: The F, B or L choice must
be equal to the F, B or L setting of
the analog input zeropoint and
fullscale.
If password protection is active, the following requires the ”level 2” password:
2.6 Base
settings
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Configurate
Base ? YES/NO
NO
Selection of changing base values.
If NO the following sub-parameters
will not be displayed.