Dig. input
5678
Failclass
3012
1111
Function, digital inputs 5 to 3.
0: Warning. Gives warning only, no inter-
ference with the present running situation.
1: As F0, but with setting of alarm output :
Common failure.
2: Stop. Trips breaker and stops genset
after cooling down time.
3: Shutdown. Trips breaker and stops
genset immediately.
Dig. input
9ABC
Function
EDEE
EEEE
Digital inputs 9 to 12 E = Energised or D =
De-energised.
Dig. input
9ABC
Delay
YYNY
NNNN
Digital inputs 9 to 12 Y = delay Yes or N =
delay No
Dig. input
9ABC
Failclass
3012
1111
Function, digital inputs 9 to 12.
0: Warning. Gives warning only, no inter-
ference with the present running situation.
1: As F0, but with setting of alarm output:
Common failure.
2: Stop. Trips breaker and stops genset
after cooling down time.
3: Shutdown. Trips breaker and stops gen-
set immediately.
DISPLAY Factory
set
Commis
sioning
value
DESCRIPTION
Dig. input
DEGF
Function
DDDD
E
Digital input 13.
E = Energised or D = De-energised.
Dig. input
DEFG
Delay
NNNN
N
Digital input 13.
Y = delay Yes or N = delay No
Dig. input
DEFG
Failclass
3333
1
Function, digital input 13.
0: Warning. Gives warning only, no inter-
ference with the present running situation.
1: As F0, but with setting of alarm output :
Common failure.
2: Stop. Trips breaker and stops genset
after cooling down time.
3: Shutdown. Trips breaker and stops gen-
set immediately.