Page 34 of 35 Tlf. (+45) 9614 9614
·
Fax:(+45) 9752 4720
·
E-mail: [email protected]
Gas delay
08 s
21s
0...99 s. Delay of gas supply after enga-
gement of start motor.
Must be a few seconds longer as the "Ign.
delay".
Starter time
03 s
05s
0...99 s. Start motor engagement time.
Start pause
time 10 s
10s
1...99 s. Delay between start attempts.
Gov. Down
bef.
Start OFF
OFF
ON/OFF. If ON is chosen, a 4 sec. signal
"speed down" will be sent to governor, before
start is attempted.
6.5 Common start/stop sequence, diesel or gas engine
DISPLAY Facto-
ry
Set
Commis-
sioning
value
DESCRIPTION
Cool down
time
180 s
030s
0...800 s. Cool down time (idle run) after
normal stop or fail with class F2. Timer
starts when generator breaker is opened.
Monitoring
Delay 15 s
08s
1...99 s. Time delay from firing speed is
reached until engine alarm and shutdown
functions are activated.
Firing speed
Reached: f>
15Hz
15Hz
15...70 Hz. Firing speed selection, related
to generator frequency.
Pickup
ON
ON
ON/OFF. Selects if the speed pickup input
is to be active. if NO the firing speed
detection will use the generator frequency.
Nom. Speed
Gen. 1/min
1500
1500
0...5000. Nominal generator RPM.
Pickup:
Number
of cogs
0030
0030
0...9999. No of cogs (teeth) on the flywheel
(normal pickup measuring point).
Mains break.
Free
Start engine
ON
ON
ON/OFF. If ON and "Auto 1" or "Auto 2" is
activated, the engine will start automatically
and close the generator breaker if the "mai-
ns breaker free" input is switched OFF. This
enables automatic island operation during
mains failure.