Programming manual MPC-1
4189340103E
G.break.blackout
Operation ON
ON
ON/OFF. Selects generator
breaker blackout start active
when ON
G.break.blackout
df max.= 0.25Hz
0.25hz
0.05...0.49Hz Blackout start
frequency deviation.
G.break.blackout
dU max. = 40V
40V
2...60 V. Blackout start
undervoltage
m.break.blackout
operation ON
ON
ON/OFF. Blackout start, mains
breaker (option A).
Sync. Time contr.
ON
ON
ON/OFF. Supervision of syn-
chronisation time of breakers
Mains trip
via GCB
GCB
GCB/MCB. Choice of trip of gen.
breaker (GCB) or mains breaker
(MCB) if a mains failure occurs.
Sync time contr.
ON
ON
ON/OFF. Choise of
synchronisation time supervision
Sync. Time contr.
Delay time 180s
120s
0...999s. Set-point of synchroni-
sation timer. At runout, alarm
"Sync. Time" and horn output is
released.
2.7.9 Emergency
power
DISPLAY Factory
set
Commis-
sioning va-
lue
DESCRIPTION
Config. emer.
Power? YES
YES
YES/NO. If NO is chosen, the
following sub-menus will not be
shown.
Emer.power
ON
ON
ON/OFF. ON: Upon mains fail, the
genset is started and used as
emergency power source.
Emergency power
start delay 15s
03s
0...99s. Start delay after mains
failure occurs.
Main
Delay time 15s
03s
0...99s. Delay after mains
restoration before re-
synchronising.
Emergency power
stop delay 10s
20s
0...99s. Stop delay after mains
restored. Emergency power supply
running time after return of the
mains.