14
Fig. 8
Meaning of the indication signals
Even if in-phase conditions occur only once, the two systems must not be connected!
5.4 Functional check
If in-phase conditions have been verified, a functional check of the indication – Out-of-phase condi
-
tions – must be performed.
>>>The yellow continuous light indicates that the device is ready for operation<<<
Contact the bare phase conductor L1 of system 1 by means of the test/contact electrode of the phase
comparator. Attach the test/contact electrode to the phase conductor until the yellow indication flashes.
The phase conductor
L2
or
L3
of system 1 must be contacted within 12 seconds!
After contacting the phase conductor, the yellow and red indication must flash and the intermittent
acoustic signal must sound. If this is the case, the functional check is completed (see Fig. 9).
>>>The two systems can be interconnected<<<
Fig. 9
Functional check
green
red
yellow
In-phase conditions
In-phase conditions are
indicated
by
the green
continuous light
!
Out-of-phase conditions
Out-of-phase conditions are indicated
by a yellow and red
flashing light
and intermittent acoustic signal
!
red
yellow
yellow
Out-of-phase conditions
Out-of-phase conditions are indicated
by a yellow and red
flashing light
and intermittent acoustic signal
!