PRO-CTR-MAN-16V03 (0128)
Copyright © 2016 Defi ne Instruments
28
F
_ _ _ SETPOINT TYPE
scrolls across the display, and the setpoint type for the
selected setpoint appears. Using the
and
buttons, select:
NORMAL
,
TIMED
or
LATCHD
(latched), and then press
.
If you selected
TIMED
or
LATCHD
, skip to 9.2I now.
If you selected
NORMAL
, continue to 9.2G now.
NORMAL
: A normal setpoint will activate and deactivate using alarm or control logic regulated
within a hysteresis band (9.2G–H).
TIMED
: A timed setpoint will activate as normal, and remain active for a user defi ned time
period (9.2K), aft er which it will deactivate automatically.
LATCHD
: A latched setpoint will activate as normal, and remain active until it is unlatched ei-
ther by setpoint logic (9.2M), or manually using a user programmable shortcut (8.5).
G
_ _ _ HYSTERESIS TYPE
scrolls across the display, and the hysteresis type for the
selected setpoint appears. Using the
and
buttons, select either
ALARM
or
CNTRL
(control), and then press
.
ALARM
-
SETPOINT VALUE
controls setpoint
activation point.
HYSTERESIS VALUE
con-
trols setpoint deactivation point.
CNTRL
-
SETPOINT VALUE
controls setpoint
deactivation point.
HYSTERESIS VALUE
con-
trols setpoint reactivation point.
Energised Above
Hysteresis
band
Energised Below
Hysteresis
band
Energised Above
Hysteresis
band
Energised Below
Hysteresis
band
H
_ _ _ HYSTERESIS VALUE
scrolls across the display, and the hysteresis value for
the selected setpoint appears. Use the
and
buttons to adjust this value if
required, and then press
.
The
HYSTERESIS VALUE
defi nes the separation band between setpoint activation and deacti-
vation, and will operate as per the
HYSTERESIS TYPE
setting selected in 9.2G.
I
_ _ _ MAKE DELAY
scrolls across the display, and the current make delay time
for the selected setpoint appears. This is the time delay between setpoint acti-
vation, and when the relay turns on. Adjust this value in 0.1 second increments
using the
and
buttons, and then press
.
If your Setpoint Type =
NORMAL
, proceed to 9.2J now.
If your Setpoint Type =
TIMED
, skip to 9.2K now.
If your Setpoint Type =
LATCHD
, skip to 9.2L now.