9.2 - Setpoint setup
A
_ _ _ EDIT SETPOINT
scrolls across the display, and
SKIP
appears. Press
now
to skip to 9.3, or use the
and
buttons to select a setpoint to edit from
1–5
, and then press
. Remember that:
›
SP 1
is a special use batch setpoint
›
SP 2–4
require relay output hardware to be installed for full functionality
›
SP 5
may be configured as an LED indicator, if desired (relay functions will
be ignored)
›
SP 6
is reserved
B
_ _ _ SP VALUE
scrolls across the display, and the current value for the selected
setpoint appears. Using the
and
buttons, adjust the display value at
which the selected setpoint will activate, and then press
.
C
_ _ _ SP ACTIVATION
scrolls across the display, and the current activation for
the selected setpoint appears. Using the
and
buttons, select the relay
activation to operate
ABOVE
or
BELOW
the setpoint value, and then press
.
If you are currently editing
SP 1
, skip to 9.2E now.
If you are currently editing
SP 2–4
, continue to 9.2D now.
ABOVE
: Relay turns on above the setpoint value and off below it.
BELOW
: Relay turns on below the setpoint value and off above it.
D
_ _ _ TRACK SP 1
scrolls across the display, and the tracking setting for the
selected setpoint appears. Using the
and
buttons, select
OFF
or
ON
, and
then press
.
If you selected
OFF
, continue to 9.2E now.
If you selected
ON
, skip to 9.2F now.
A setpoint with
TRACK SP 1
enabled will track the setpoint value of
SP 1
, with the setpoint
value of the tracking setpoint becoming an off set value.
E
_ _ _ SETPOINT SOURCE
scrolls across the display, and the activation source for
the selected setpoint appears. Use the
and
buttons to choose
PRMCTR
,
B CNTR
,
C CNTR
,
RATE
,
BATCH
or
BCHCNT
, and then press
.
See 7.1 for more information on the batching feature.