37
5
Fault elimination
Display
Description
Radio sensor K1
ESC Install? OK
Cause:
If a new battery is inserted into the radio humidity sensor (op-
tion) and the radio channel of the radio humidity sensor does
not correspond to the active channel of the PH... a beep sounds
briefly (if the buzzer is activated) and a new radio channel (e.g.
K1) will be proposed.
Action:
Press the
<Enter>
key if you want to confirm the suggested
channel. The PH... switches to the new channel and returns to
the standard operating display.
Press the
<ESC>
key if you want to reject the suggested chan-
nel. The PH... returns to the standard operating display and uses
the old signal source.
Radio sensor K1
Test
Cause:
If a new battery is inserted into the radio humidity sensor (op-
tion) and the radio channel of the radio humidity sensor does
correspond to the active channel of the PH... a beep sounds
briefly (if the buzzer is activated) and the unit confirms the cor-
rect channel.
Action:
To reset the message and to return to the standard operating
display press the
<Enter>
or the
<ESC>
key.
5.1
Event messages
5.2
Warning messages
Display
red LED
Buzzer
Error relay
Resetting
Warning 6
Filter change
Warning message is alter-
nating with the standard
operating display.
lights
–––
activated
see chapter 6.5 in the
operating instructions.
Cause:
Maximum lifetime of the filter set expired.
Action/Remedy: Replace filter set (see chapter 6 “Maintenance” in the operating instructions), then reset
warning message.
Warning 7
No water
Warning message is dis-
played until the water level in
the base tub is ok. again.
lights
–––
activated
Automatic resetting as
soon as the water level
in the base tub is at normal
level again.
Note:
This message is displayed only on the PH15, PH27 and PH28
Cause:
The water level in the base tub is too low, level switch has triggered.
Action/Remedy: Check/refill water tank. Check/clean level switch.
Warning 8
Battery radio
Warning message is alter-
nating with the standard
operating display.
lights
beeps briefly
every 30 min-
utes
activated
Automatic resetting af-
ter replacement of the
battery.
Cause:
Battery in radio humidity sensor (option) is empty.
Action/Remedy: Replace battery of the radio humidity sensor (see separate instructions of radio humidity
sensor).