22
1. In the normal operation display press simultaneously the and
keys until the code entry display appears (> 3 seconds) .
2. Enter the code “8808” and confirm with the
<Enter>
key, to call the
service level.
3. In the service level select the menu item “Act.Value Source” with
or key, then press the
<Enter>
key.
4. Select the desired channel (Radio 1 ... Radio 4) using the or
key and confirm the selection with the
<Enter>
key.
5. Press the
<Esc>
key multiple times to return to the normal operation
display.
Modifying the channel at the radio humidity sensor
1. Open the battery compartment and remove the battery.
2. Undo the screw and remove the housing cover.
Attention!
The electronic components on the control board of the radio humidity sensor are
very susceptible to electrostatic discharges. For the protection of these components, measures
must be taken for the work on the control board to prevent damage caused by electrostatic
discharge (ESD–protection).
3. Set the channel via the DIP switches on the control board (see illustration above).
4. Attach the housing cover and fix it with the screw.
5. Insert the battery (
observe
correct polarity
), then close the battery compartment.
Modifying the channel setting on the PH...
O
N
1
2
O
N
1
2
O
N
1
2
O
N
1
2
Channel 1
Channel 2
Channel 3
Channel 4
^ Act 38%rH HA
Set 45%rH
^ Act 38%rH HA
Set 45%rH
PHXX
^ Set 38%rH HA
PHXX
^ Set 38%rH HA
Code
8808
Act.Value Source
Radio 2
Act.Value Source
Radio 2
PH28/PH28A
PH28/PH28A
PH15/PH15A / PH27/PH27A
PH15/PH15A / PH27/PH27A