Error
code
Description
Probable causes
Checking / solution
e[08
Return temperature too low
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
e[09
Return temperature too high
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
e[10
Difference insufficient between the
exchanger temperature and the
return temperature
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
Bad connection
4
Check that the sensor has been correctly fitted
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
e[11
Difference between the return
temperature and the exchanger
temperature too big
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
Bad connection
4
Check that the sensor has been correctly fitted
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
IniControl For C 330 / C 630 ECO
6. Troubleshooting
260216 - 7600717-001-06