Parameter
Description
Adjustment range
Factory setting
C 630 ECO
560 700 860 1000 1140 1300
p40
Maintenance message
0 = Service messages off
1 = Service messages on
0
0
0
0
0
0
p41
Service operating hours
( x 100)
Do not modify
175 175 175 175
175
175
p42
Service burning hours
( x 100)
Do not modify
30
30
30
30
30
30
p43
Setting the pump speed
(Minimum pump speed for
central heating operation)
2 - 10 (x 10%)
2
2
2
2
2
2
p44
Setting the pump speed
(Maximum pump speed for
central heating operation)
6 - 10 (x 10%)
10
10
10
10
10
10
p45
ΔTModulate down
10 to 30 °C
25
25
25
25
25
25
Zd
Detection of connected
SCUs
0 = No detection
1 = Detection
0
0
0
0
0
0
df
and
dV
Factory setting
To restore the factory settings or when
replacing the main PCB, enter the values
dF and dU from the type plate in parameters
df
and
dV
X
X
X
X
X
X
Y
Y
Y
Y
Y
Y
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
5.4.3.
Modification of the user-level parameters
Parameters
p001
to
p007
can be changed by the user.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
5. Commissioning
IniControl For C 330 / C 630 ECO
23
260216 - 7600717-001-06