Parameter
Description
Adjustment range
Factory setting
C 630 ECO
560 700 860 1000 1140 1300
p22
Heat curve set point
(Maximum outside
temperature)
(Only with an outside
temperature sensor)
0 to 30 °C
20
20
20
20
20
20
p23
Heat curve set point
(Flow temperature)
(Only with an outside
temperature sensor)
0 to 90 °C
20
20
20
20
20
20
p24
Heat curve set point
(Minimum outside
temperature)
(Only with an outside
temperature sensor)
-30 to 0 °C
-15 -15 -15 -15
-15
-15
p25
Antifreeze temperature
(Only with an outside
temperature sensor)
from - 30 to 0°C
- 10 - 10 - 10 - 10 - 10 - 10
p26
Fault relay function
X4
(If connected)
0 = Operation signal
1 = Alarm signal
0
0
0
0
0
0
p27
Fault relay function
X5
(If connected)
0 = Operation signal
1 = Alarm signal
1
1
1
1
1
1
p28
Minimum water pressure
Wps
(Only with the hydraulic
pressure sensor
connected)
0 - 3 bar (MPa) (x 0,1bar (MPa))
0 = Not connected
0
0
0
0
0
0
p29
Minimum gas pressure
check Gps
0 = Not connected
1 = Connected
0
0
0
0
0
0
p30
Hydraulic valve running
time HdV
(If connected)
0 to 255 seconds
0
0
0
0
0
0
p31
Flue gas damper running
time FgV
(If connected)
0 to 255 seconds
0
0
0
0
0
0
p32
Release waiting time
0 to 255 seconds
0
0
0
0
0
0
p33
Gas valve leak proving
system CCE
0 = Not connected
1 = Connected
0
0
0
0
0
0
p34
Live/neutral inversion
0 = Off
1 = On
0
0
0
0
0
0
p35
Shutdown input function
1 = Shutdown without frost-protection
2 = Shutdown with frost protection
3 = Lock-out with frost protection (Pump
only)
1
1
1
1
1
1
p36
From Analogue output (0 -
10V)
SCU-S05 control PCB
0 =0-10 V Wilo control PCB
1 = 0-10 V Grundfoss control PCB
2 = PWM pump
3 = Heat output feedback
4 = Temperature feedback
0
0
0
0
0
0
p37
From Analogue input
(0-10V)
SCU-S05 control PCB
0 =OpenTherm regulator
1 = Analogue temperature-based control
(°C)
2 = Analogue heat output-based control (%)
0
0
0
0
0
0
p38
Boiler inertia
Do not modify
6
6
6
6
6
6
p39
Display units
0 =
À
/ bar
1 = F / PSI
0
0
0
0
0
0
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
IniControl For C 330 / C 630 ECO
5. Commissioning
260216 - 7600717-001-06
22