5.4.6.
Return to the factory settings Reset Param
1. Press the two keys
f
simultaneously and then key
[+]
until the
symbol
-
flashes on the menu bar.
2. Select the installers menu using the key
S
.
c0de
appears
on the display.
3. Use keys
[-]
or
[+]
to input the installer code
0012
.
4. Confirm using key
S
.
p[1
is displayed with
1
flashing.
5. Press the
[+]
key several times.
p[Cnnf
is displayed with
Cn1
flashing.
6. Press the
S
key.
Cn[x
is displayed with
x
flashing. This is
the current value of X for CN1. Check this against the value of X
on the type plate.
7. Enter the value of X shown on the type plate using the
[-]
or
[+]
key.
8. Confirm the value with the
S
key,
Cn[y
is displayed with
y
flashing. This is the current value of Y for CN2. Check this against
the value of Y on the type plate.
9. Enter the value of Y shown on the type plate using the
[-]
or
[+]
key.
10.Confirm the value with the
j
key. The factory settings are reset.
11.The display returns to the current operating mode.
5.4.7.
Carrying out an auto-detect
After removing a control PCB, an auto-detect must be carried out. To
do this, proceed as follows:
1. Press the two keys
f
simultaneously and then key
[+]
until the
symbol
-
flashes on the menu bar.
2. Select the installers menu using the key
S
.
c0de
appears
on the display.
3. Use keys
[-]
or
[+]
to input the installer code
0012
.
4. Confirm using key
S
.
p[1
is displayed with
1
flashing.
5. Press the
[+]
key several times.
p[Zd
is displayed with
Zd
flashing.
6. Confirm using key
j
. Auto-detect is carried out.
7. The display returns to the current operating mode.
C003062-A
3x
...x
-
IniControl For C 330 / C 630 ECO
5. Commissioning
260216 - 7600717-001-06
26