![DeDietrich C 340 280 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/dedietrich/c-340-280/c-340-280_installation-and-user-manual_2462417033.webp)
Tab.28
On > > Installation Setup > SCB-10 > CIRCA > Parameters, counters, signals > Parameters
Code
Display text
Description
Range
Setting
CP000
MaxZoneTFlowSetpoint
Maximum Flow Temperature setpoint
zone
7 °C - 100 °C
50
CP010
Tflow setpoint zone
Zone flow temperature setpoint, used
when the zone is set to a fixed flow
setpoint.
7 °C - 100 °C
40
CP020
Zone Function
Functionality of the zone
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Temperature
5 = Fan Convector
6 = DHW tank
7 = Electrical DHW
8 = Time Program
9 = ProcessHeat
10 = DHW Layered
11 = DHW Internal tank
31 = DHW FWS EXT
2
CP230
Zone Heating Curve
Heating curve temperature gradient of
the zone
0 - 4
0.7
4 Preparation of installation
7762666 - v.02 - 29092020
C 340 / C 640