L Combined length of the flue and air supply channel to the roof
terminal
Flue gas outlet connection
Air supply connection
Tab.18 Maximum length (L)
Diameter
300 mm
350 mm
400 mm
C 640 560
100 m
100 m
C 640 700
86 m
100 m
C 640 860
52 m
100 m
C 640 1000
26 m
70 m
100 m
C 640 1140
10 m
32 m
48 m
C 640 1300
-
20 m
24 m
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º
bends can be used (indicated for each boiler type and diameter).
Connection in different pressure zones (C
53
)
The maximum permitted height difference between the air supply terminal
and the flue gas outlet is 36 m.
L Combined length of the flue and air supply channel
Flue gas outlet connection
Air supply connection
Tab.19 Maximum length (L)
Diameter
180 mm 200 mm 250 mm 300 mm
C 340 280
32 m
61 m
C 340 350
14 m
30 m
C 340 430
8 m
20 m
88 m
C 340 500
-
16 m
76 m
C 340 570
-
10 m
53 m
C 340 650
-
5 m
38 m
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º
bends can be used (indicated for each boiler type and diameter).
L Combined length of the flue and air supply channel
Flue gas outlet connection
Air supply connection
Tab.20 Maximum length (L)
Diameter
300 mm
350 mm
400 mm
C 640 560
100 m
100 m
C 640 700
48 m
100 m
C 640 860
24 m
83 m
100 m
C 640 1000
-
38 m
90 m
C 640 1140
-
-
28 m
C 640 1300
-
-
-
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º
bends can be used (indicated for each boiler type and diameter).
Reduction table
Tab.21 Pipe reduction for each bend - radius 1D (parallel)
Diameter
150
mm
180
mm
200
mm
250
mm
300
mm
350
mm
400
mm
45° bend
1.2 m 1.4 m 1.6 m 2.0 m 2.4 m 2.8 m 3.2 m
90° bend
2.1 m 2.5 m 2.8 m 3.5 m 4.2 m 4.9 m 5.6 m
Fig.17
Room-sealed system C 640
AD-3001565-01
L = +
Fig.18
Different pressure zones C 340
AD-3001563-01
L = +
Fig.19
Different pressure zones C 640
AD-3001566-01
L = +
Fig.20
Bend radius 1D
AD-3001609-01
D
R=1D
4 Preparation of installation
7762666 - v.02 - 29092020
C 340 / C 640
25