Code
Display text
Description
Range
Submenu
Default
setting
CP020
CP021
CP022
CP023
CP024
Zone Function
Functionality of the zone
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Temperature
5 = Fan Convector
6 = DHW tank
7 = Electrical DHW
8 = Time Program
9 = ProcessHeat
10 = DHW Layered
11 = DHW Internal tank
12 = DHW Commercial
Tank
13 = DHW FWS
31 = DHW FWS EXT
255 = Occupied
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
1
0
0
0
0
CP030
CP031
CP032
CP033
CP034
Bandwidth Mix.
Valve
Bandwidth of mixing valve zone
where modulation takes place.
4 °C - 16 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
12
12
12
12
12
CP040
CP041
CP042
CP043
CP044
Postrun zone
pump
Pump post runtime of the zone
0 Min - 20 Min
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
4
4
4
4
4
CP050
CP051
CP052
CP053
CP054
Mixing Valve shift Shift between calculated setpoint and
mixing valve circuit setpoint
0 °C - 16 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
4
4
4
4
4
CP060
CP061
CP062
CP063
CP064
RoomT. Holiday
Wished room zone temperature on
holiday period
5 °C - 20 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
6
6
6
6
6
CP070
CP071
CP072
CP073
CP074
MaxReducedRoo
mT.Lim
Max Room Temperature limit of the
circuit in reduced mode, that allows
switching to comfort mode
5 °C - 30 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
16
16
16
16
16
CP210
CP211
CP212
CP213
CP214
Zone HCZP
Comfort
Comfort footpoint of the temperature
of heat curve of the circuit
15 °C - 90 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
15
15
15
15
15
CP220
CP221
CP222
CP223
CP224
Zone HCZP
Reduced
Reduced footpoint of the temperature
of heat curve of the circuit
15 °C - 90 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
15
15
15
15
15
CP230
CP231
CP232
CP233
CP234
Zone Heating
Curve
Heating curve temperature gradient
of the zone
0 - 4
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
1.5
0.7
1.5
0.7
1.5
CP240
CP241
CP242
CP243
CP244
ZoneRoomUnitInf
l
Adjustment of the influence of the
zone room unit
0 - 10
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
3
3
3
3
3
10 Settings
108
C 340 / C 640