Code
Display text
Description
Range
Submenu
CM120
ZoneCurrentMode
Zone Current Mode
0 = Scheduling
1 = Manual
2 = Antifrost
3 = Temporary
Direct zone
CM130
ZoneCurrent activi
ty
Current activity of the zone
0 = Anti frost
1 = Reduced
2 = Comfort
3 = Anti legionella
Direct zone
CM190
Zone Troom set
point
Wished room temperature setpoint of the
zone
5 - 30 °C
Direct zone
CM210
ZoneTout temp
Current outdoor temperature of the zone -70 - 70 °C
Direct zone
Tab.110 Navigation for installer level
Level
Menu path
Installer
> Installation Setup > CU-GH13 > Submenu
> Parameters, counters, signals > Signals
(1) See the column "Submenu" in the following table for the correct navigation. The signals are grouped in specific functionalities.
Tab.111 Signals at installer level
Code
Display text
Description
Range
Submenu
AM036
Flue gas tempera
ture
Temperature of the exhaust gas leaving
the appliance
0 - 250 °C
Gas fired ap
pliance
AM044
Nr sensors suppor
ted
Number of sensors supported by the de
vice
0 - 255
Gas fired ap
pliance
AM045
Water P available
Water pressure sensor present?
0 = No
1 = Yes
Gas fired ap
pliance
CM070
Zone Tflow Set
point
Current Flow temperature setpoint of
zone
0 - 150 °C
Direct zone
CM140
ZoneOTContr
present
OpenTherm controller is connected to
the zone
0 = No
1 = Yes
Direct zone
CM150
ZoneState Heatde
mand
State of On Off heat demand per zone
0 = No
1 = Yes
Direct zone
CM160
Zone Mod HeatDe
mand
Presense of modulating heat demand
per zone
0 = No
1 = Yes
Direct zone
CM200
ZoneCurrentHeat
Mode
Displaying current operating mode of the
zone
0 = Standby
1 = Heating
2 = Cooling
Direct zone
GM001
Actual fan RPM
Actual fan RPM
0 - 8500 Rpm
Gas fired ap
pliance
GM002
Fan RPM setpoint
Actual fan RPM setpoint
0 - 8500 Rpm
Gas fired ap
pliance
GM008
Actual flame cur
rent
Actual flame current measured
0 - 25 µA
Gas fired ap
pliance
NM001
CascSystemTF
Cascade system flow temperature
-10 - 120 °C
Producer Ge
neric
Produc
er<>Consum
er
PM002
CH Setpoint
Central heating setpoint of the appliance 0 - 125 °C
Gas fired ap
pliance
Tab.112 Navigation for advanced installer level
Level
Menu path
Advanced installer
> Installation Setup > CU-GH13 > Submenu
> Parameters, counters, signals > Adv. Signals
(1) See the column "Submenu" in the following table for the correct navigation. The signals are grouped in specific functionalities.
10 Settings
7762666 - v.02 - 29092020
C 340 / C 640