Code
Display text
Description
Range
Submenu
Default
setting
AP091
Outside Sens.
Source
Type of outside sensor connection to
be used
0 = Auto
1 = Wired sensor
2 = Wireless sensor
3 = Internet measured
4 = None
Outdoor
temperature
0
BP001
Type Buffer Tank Type of buffer tank
0 = Disabled
1 = One sensor
2 = Two sensors
3 = Three sensors
4 = Four sensors
Disabled
buffer tank
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
0
BP002
Buff Tank HC
Strat.
Heating Cooling Control strategy
used with buffer tank
0 = Fixed setpoint
1 = Calculated setpoint
2 = Dedicated slope
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
0
BP003
Stp Buffertank
Heat
Temperature setpoint for buffer tank
in heating mode
5 °C - 100 °C
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
70
BP004
Setp Buffertank
Cool
Temperature setpoint for Buffer tank
in cooling mode
5 °C - 25 °C
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
18
BP005
Buffer Tank Slope Buffer Tank Slope
0 - 4
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
1.5
BP013
BufferTankTcalOf
fset
Offset to add to the calculate Setpoint
of the Buffer Tank
0 °C - 20 °C
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
5
BP014
BufferTank
HystStart
Hysteresis of temperature which
determines the start of Buffer Tank
storage
1 °C - 20 °C
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
6
BP015
Buf.Tank post run Minimum duration of post-operation
of the buffer tank pump
0 Min - 20 Min
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
4
BP019
BufferTank
HystStop
Hysteresis of temperature which
determines the stop of buffer tank
storage
-30 °C - 30 °C
Pass.buff.tan
k 1sens
Pass.buff.tan
k 2sens
0
CP000
CP001
CP002
CP003
CP004
MaxZoneTFlowS
etpoint
Maximum Flow Temperature setpoint
zone
7 °C - 100 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
90
50
95
50
95
10 Settings
7762666 - v.02 - 29092020
C 340 / C 640
107