6

1.

 

The fryer and its individual shut-off
valve must be disconnected from the
gas supply piping system during any
pressure testing of that system at
pressures in excess of ½ PSIG
(3.45KPa).

2.

 

The fryer must be isolated from the gas
piping system by closing its individual,
manual shut-off valve during any
pressure testing of the gas supply
piping system at pressures equal to
more than ½ PSIG (3.45KPa).

b.

 

Manual shut-off valve: This supplier-
installed valve must be installed in the gas
service line ahead of the appliance in the
gas stream and in a position where it can
be reached quickly in the event of an
emergency.

c.

 

Pressure regulating:

1.

 

External regulators are not normally
required on this fryer, as that function
is performed by a safety control valve.

2.

 

Exception:

  

If the incoming pressure

is in excess of ½” PSIG (3.45KPa), a
step-down regulator will be
required.

  

Your local servicer

should check the manifold pressure
with a manometer – natural gas
units require 3.5” WC (8.71mbar)
and propane requires 10” WC
(25mbar).

d.

 

Orifices: The fryer can be connected to
either natural or propane gas. The correct
safety control valve and appropriate gas
orifices are installed at the factory.  While
the valve can be adjusted in the field, only
qualified service personnel should make
any adjustment with the proper test
equipment.

e.

 

Rigid Connections: The fryer can be
connected singly or as part of a cooking
line.  Check any installer-supplied intake
pipe(s) visually and clean threading chips

or any other foreign matter before
installing into a service line.

f.

 

Flexible Couplings & Connectors:

1.

 

If the unit is installed with couplings
or quick disconnect fittings, the
installer must  use a heavy-duty, AGA
design-certified commercial connector
of at least ¾” NPT (with suitable
strain relief) in compliance with ANSI
Z-21.69-1979.   Domestic connectors
are not suitable.

2.

 

If the unit is installed with casters, the
installation should be made with a
connector that complies with the
Standard for Connectors for Moveable
Gas Appliances, ANSI Z21.69 or
Connectors for Moveable Gas
Appliances, CAN/CGA-6.16, and a
quick-disconnect device that complies
with the Standard for Quick
Disconnect Devices for Use with Gas
Fuel, ANSI Z21.41, or Quick
Disconnect for Use with Gas Fuel,
CANI-6.9, adequate means must be
provided to limit the movement of the
appliance without depending on the
connector and the quick disconnect
device or its associated piping to limit
the appliance movement.  A
restraining bracket is provided on the
appliance structural back to prevent
the unit from moving from its
installed position.

CAUTION

ALL CONNECTIONS MUST BE SEALED
WITH A JOINT COMPOUND SUITABLE
FOR LP GAS, AND ALL CONNECTIONS
MUST BE TESTED WITH A SOAPY
SOLUTION BEFORE LIGHTING ANY
PILOTS.

Содержание Super Runner 38 Series

Страница 1: ...Commercial Food Equipment Service Association recommends using CFESA Certified Technicians Price 6 00 24 Hour Service Hotline 1 800 551 8633 819 5645 04 98 Super Runner 38 Series Gas Fryers Installat...

Страница 2: ...TO BE POSTED IN A PROMINENT LOCATION THIS INFORMATION SHALL BE OBTAINED BY CONTACTING THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND...

Страница 3: ...r call the factory The factory address and phone numbers are on the cover of this manual To speed up your order the following information is required Model Number Serial number Type of Gas Item Part N...

Страница 4: ...supply line ahead of the fryer s for safety and ease of future service 2 The Model SR38G gas fryers are equipped with millivolt controls which do not require electrical power connections and do not h...

Страница 5: ...d installing a hood The duct system the exhaust hood and the filter bank must be cleaned on a regular basis and kept free of grease e Adequate distance must be maintained from the flue outlet of the f...

Страница 6: ...about one inch of adjustment thread When leveling the unit the leg body should be held firmly to keep it from rotating while turning the 5 8 bottom leg hex nut counter clockwise Turn the hex nut to ad...

Страница 7: ...djustment with the proper test equipment e Rigid Connections The fryer can be connected singly or as part of a cooking line Check any installer supplied intake pipe s visually and clean threading chip...

Страница 8: ...eaving the factory Adjustments to assure proper operation may be necessary on installation to meet local conditions low gas pressure differences in altitude variations in gas characteristics to correc...

Страница 9: ...ger before releasing It may be necessary to re light the pilot several times until the lines are purged of trapped air and a constant gas flow is attained 8 When the pilot stays lit turn the gas cock...

Страница 10: ...c until the shortening is melted If you see any smoke coming from the oil while melting this way shorten the ON cycle and lengthen the OFF cycle Smoke shows that you are scorching the shortening and r...

Страница 11: ...sure the filter unit is aligned properly with the drain valve Attach the drain valve extension to the drain valve to ensure hot oil shortening flows into the filter unit safely b Proper filtering assu...

Страница 12: ...rvicing the restraining device has to be removed from the bracket and both front casters locking mechanisms have to be turned OFF To return the unit to its previous installed position see sections 3 3...

Страница 13: ...the day and with a liquid cleaner designed for this material at the end of each day a Do not use steel wool abrasive cloths cleansers or powders b Do not use a metal knife spatula or any other metal t...

Страница 14: ...ilot flame go out when gas cock manual knob is released Check that the thermocouple lead is properly screwed into the gas control valve bushing Remove the end of the thermocouple lead from the gas con...

Страница 15: ...Contact your local gas supplier or authorized Dean servicer Problem is caused by drafts Turn ON air conditioning and make up air systems and correct drafts Fryer is good Conduct normal cooking operat...

Страница 16: ...local authorized Dean servicer or local gas supplier Turn the gas cut off valve OFF Turn the gas cut off valve to the OPEN position Turn the fryer s combination gas valve manual knob to OPEN Problem i...

Страница 17: ...t Using a thermometer or external temperature probe recalibrate the thermostat Set the thermostat and verify set temperature once fryer warms up Does the thermostat maintain set temperature Replace th...

Страница 18: ...17 6 6 MILLIVOLT DIAGRAM Thermopile Black Black Red Red Red White Operating Thermostat Hi Limit Combination Gas Valve...

Страница 19: ...18 Notes...

Страница 20: ...ies 14501 South Broadway Gardenia California 90248 TEL 1 310 323 5000 FAX Parts 1 310 327 3343 FAX Tech Support 1 318 219 7135 Price 6 00 PRINTED IN THE UNITED STATES SERVICE HOTLINE 1 800 551 8633 81...

Отзывы: