24G SERIES FLATBOTTOM GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3-6
3.4 Gas Connections (cont.)
DANGER
All connections must be sealed with a joint compound suitable for the gas being
used and all connections must be tested with a solution of soapy water before
lighting any pilots.
Never use matches, candles, or any other ignition source to check for leaks. If gas
odors are detected, shut off the gas supply to the appliance at the main shut-off
valve and immediately contact the local gas company or an authorized service
agency for service.
DANGER
"Dry-firing" your unit will cause damage to the frypot and can cause a fire. Always
ensure that melted shortening, cooking oil or water is in the frypot before firing the
unit.
Rigid Connections
Check any installer-supplied intake pipe(s) visually and clean metal particles or other foreign matter
from the threads before installing into a service line. If the intake pipes are not clear of all foreign
matter, the orifices will clog when gas pressure is applied. When using thread compound on gas
piping, use very small amounts and only on male threads. Use a pipe thread compound that is not
affected by the chemical action of propane/LP (G31) gases. DO NOT apply thread compound to the
first two pipe threads – doing so will cause clogging of the burner orifices and control valve.
Manual shut-off valve
This gas service supplier-installed valve must be installed in the gas service line ahead of the fryers
in the gas stream and in a position where it can be reached quickly in the event of an emergency.
Regulating Gas Pressure
The fryer and shut-off valve must be disconnected from the gas supply during any pressure testing of
the system.
WARNING
If the incoming gas pressure is in excess of ½" PSI (3.45 kPa/35 mbar), a step-down
regulator will be required.
External gas regulators are not normally required on this fryer. A safety control valve protects the
fryer against pressure fluctuations. If the incoming pressure is in excess of ½" PSI (3.45 kPa/35
mbar),
a step-down regulator will be required
.