background image

11

O W N E R ’ S   M A N U A L

DCA500WH - DCA14000WH INSTALLATION POOL WATER
HEATING DEHUMIDIFIERS

POOL WATER PIPING:

Schedule 40 CPVC thermoplastic or copper piping is

recommended. Standard PVC, aluminum, galvanized, black
iron and cast iron piping must not be used.

The O.D. size of the supply and return water piping must

not be downsized from the connection on the DCA
Dehumidifier. If the main by-pass valve is more than 10 feet
from the dehumidifier, increase the pipe size one size up.
Both the supply and return pipe should be insulated for
best results.

It is very important that the water flow be verified and

matches the chart below.

IMPORTANCE OF POOL WATER CHEMISTRY

It is the responsibility of the indoor pool, spa, whirlpool

or water park owner to maintain correct pool water
chemistry. Poor pool water quality caused by out of
balance pool or spa water chemistry is a serious health
and comfort problem. Many times the so called offensive
“pool water smell” is a tip off that this water chemistry
needs attention. It is the responsibility of the pool or spa
manager to test the water chemistry daily with a pool water
test kit. This kit will analyze PH - total alkalinity - free
available and combined chlorine in the water. Proper pool
water treatment procedures can only be obtained from the
pool, spa or whirlpool equipment or pool water chemical
suppliers. With this also is the verification of proper pool or
spa water temperature.

Poor pool or spa water chemistry will result in the

formation of scale and corrosion within the dehumidification
system which will drastically shorten the effective service
life of the dehumidifier.

FAILURE TO FOLLOW THE ABOVE
RECOMMENDATIONS WILL RESULT IN THE
VOIDING OF ALL WARRANTIES FROM DCA THAT
WERE EITHER EXPRESSED, IMPLIED OR WRITTEN.

STORAGE OF POOL OR SPA WATER CHEMICALS:

This is an area of swimming pool or spa management

that most times is either neglected or forgotten about
altogether with often dire consequences. Pool water
chemicals, by their very nature, are some of the most
corrosive chemicals that are available for non-professional
use.

Under no circumstances should the storage of spa or

pool water chemicals be in the same room with the

dehumidifier. The very corrosive effects of these
disinfectant will quickly attack any and all metal surfaces it
comes in contact with. Not only will the dehumidification
system be effected, but also any pool or spa water heating
systems, pumps or other mechanical devices such as
controls be adversely affected.

Proper storage must be in another area of the building or

in a sealed non-metallic cabinet that will ensure that no
vapor release of the chemicals will occur. It will be easy to
detect, if the early failure of equipment occurs, that
improper chemical storage was the cause.

FAILURE TO FOLLOW THE ABOVE
RECOMMENDATIONS WILL RESULT IN THE
VOIDING OF ALL WARRANTIES FROM DCA THAT
ARE EITHER EXPRESSED, IMPLIED OR WRITTEN.

DCA

DCA

DCA

DCA

DCA

DCA

DCA

3300WH

DCA

4000WH

DCA

DCA

DCA MODEL #

900WH

1400WH

2000WH 2500WH

3000WH

3500WH

3800WH

4200WH

5400WH 7000WH

GPM at
25°F Diff.

4.0

5.0

8.0

11.0

11.0

15.0

17.0

21.0

24.0

36.0

Pipe Pressure Drop
ft. H

2

O

7.0

4.0

7.7

6.5

8.2

8.2

6.7

7.7

10.7

12.4

DCA

DCA

DCA

DCA

DCA

DCA

DCA

DCA

DCA MODEL #

8000WH(A) 8000WH(B) 9000WH(A)

9000WH(B) 11000WH(A) 11000WH(B) 14000WH(A) 14000WH(B)

GPM at
25°F Diff.

17.0

17.0

21.0

21.0

17.0

36.0

36.0

36.0

Pipe Pressure Drop
ft. H

2

O

6.7

6.7

7.7

7.7

6.7

12.4

12.4

12.4

Содержание DCA500

Страница 1: ...I N S T A L L A T I O N O P E R A T I O N M A I N T E N A N C E SWIMMING POOL DEHUMIDIFIER OWNER S MANUAL...

Страница 2: ...ing Of Remote Condenser And Charging Instructions 7 Air Flow Balancing 8 9 Unit Start Up Procedure 10 Maintenance And Service Procedure 10 Pool Water Heating Dehumidifier Procedure 11 Pool Chemical St...

Страница 3: ...air The heat recovered by the above mentioned process known as latent heat and the electrical consumption of the compressor is delivered by the reheat condenser coil The air leaving the evaporator coi...

Страница 4: ...ool an approved drain must be provided for proper disposal If codes permit schedule 40 PVC pipe is recommended for drainage pipe Slope the condensate drain line with a minimum of 1 4 inch per foot A P...

Страница 5: ...te controls in a room that is not being conditioned by the dehumidification system unless system has remote sensors optional Controls should be mounted 5 feet from floor level on an interior wall All...

Страница 6: ...air does not short cycle back to the return inlet If dehumidifier is installed without return air duct provide a minimum of 4 feel clearance between unit and closest obstruction 3 The recommended duct...

Страница 7: ...Or Less 20 Or Less Discharge Discharge 5W Or More For Static Pressure Regain Intake TYPICAL DUCTED POOL ROOM INSTALLATION SMACNA DUCT DESIGNS DCA Dehumidifier Recommended Recommended Recommended Recom...

Страница 8: ...re that all solder joints are clean oil free and absent of any foreign material Insert copper into valve until line bottoms out in valve Complete soldering process Pressurize line set to determine if...

Страница 9: ...g Port Locations Return A L LO B HI CHART A Shows the location of the air balancing access ports and where to insert the HI and LO pressure tubes of the monometer or gauge Measure the pressure differe...

Страница 10: ...ed Under no circumstances should the unit be run for temporary heat when building construction is in progress or when there is no water in the pool HUMIDISTAT This control turns the unit on or off whe...

Страница 11: ...at to normal settings Typically between 50 RH and 60 RH and 82 F to 88 F MAINTENANCE AND SERVICE PROCEDURE Your DCA Dehumidifier requires minimal maintenance The following areas should be checked as r...

Страница 12: ...f the dehumidifier FAILURE TO FOLLOW THE ABOVE RECOMMENDATIONS WILL RESULT IN THE VOIDING OF ALL WARRANTIES FROM DCA THAT WERE EITHER EXPRESSED IMPLIED OR WRITTEN STORAGE OF POOL OR SPA WATER CHEMICAL...

Страница 13: ...Others A Air Filter B Damper Control and Timer C Outside Air Pre Heater D Bird Screen Termination 8 Mounting feet and vibratiobn isolators by others 9 Electric Gas Hot Water Add On Duct Heater By Othe...

Страница 14: ...witch in in off position automatic position Unit does not shut off Malfunctioning controls Call service technician to repair or replace control Unit not operating properly Humidistat turned off Turn h...

Страница 15: ...capacitor transformer or compressor Dehumidifying coil iced up Return air below 45 F Raise return air temperature Filters dirty or clogged Replace filters Low air flow Check blower motor and belt Adju...

Страница 16: ...Change blower rotation 3 phase only Motor going off on internal Check for rated AMP draw overload Replace motor if defective Dirty filters Replace filters Supplyandreturnairregisters Remove restrictio...

Страница 17: ...y filters Replace filters High humidity in space Incorrect duct work Check duct work design See manual Low air flow Adjust blower Check blower motor and pulley Dirty filters Replace filters Outdoor co...

Страница 18: ...be at the discretion of DCA and will be handled on a case by case basis Normally after the second compressor fails within the 3 year warranty period a problem exists in the installation maintenance o...

Страница 19: ...nusual use of supplemental heat 7 Actions or negligence of the installer or servicer of the unit that result in losses or damage of any kind including those due to inadequate A Sizing of the unit to t...

Страница 20: ...low if required must be established 6 Duct work including duct grills and diffusers must be completed 7 A thorough leak check should be performed Due to the fact that the unit may be damaged while in...

Страница 21: ...Giuffre PE Engineering 262 377 7501 tgiuffre dehumidifiercorp com Graham Gelhaar Service 262 377 7501 ggelhaar dehumidifiercorp com Jim Metzger Sales 262 377 7501 jmetzger dehumidifiercorp com Fax 26...

Отзывы: