O W N E R ’ S   M A N U A L

FAN SWITCH

ON 

- Blower runs continuously regardless of temperature

or humidity setting.

AUTO 

- Blower will operate only when thermostat is calling

for Heating or Cooling or Humidistat is calling for
Dehumidification.

UNIT START-UP PROCEDURE

Read this manual carefully
before attempting to operate the Dehumidifier. Startup
report must be completed and returned to DCA or warranty
is void.

The following check list must be verified
before start-up of unit.

1. Power supply connected and compared with unit 

nameplate voltage requirement. (See unit 
specifications)

2. Unit properly grounded.

3. Check and tighten all factory and field wiring 

connections.

4. Clean air filters installed.

5. Check and adjust belt tension. Belt should deflect 

approximately 3/4” to 1” midway on the belt.

6. Condensate drain line is free of obstructions and is 

leak free.

7. check level or pitch of unit to be sure that 

condensate water flows freely from outlet of drain. A
simple test is to pour water into drain pan of unit and
verify that water flows out of unit. This will also fill 
the P-Trap.

8. Outdoor remote condenser properly grounded. (If 

equipped)

9. Power supply connected to remote condenser as per

nameplate. (If equipped)

10. Set humidistat below room condition. Unit should 

start in reheat condenser mode if remote condenser 
equipped.

11. Set thermostat below room condition. Unit should 

start if remote condenser equipped.

12. check temperature of air in heat mode. Temperature 

should be 10°F to 20°F lower than room 
temperature.

13. Check temperature of air in cooling mode (If 

equipped). Temperature should be 10°F to 20°F 
lower than room temperature.

14. Return humidistat and thermostat to normal settings. 

Typically between 50% RH and 60% RH and 82°F to 88°F.

MAINTENANCE AND SERVICE PROCEDURE

Your DCA Dehumidifier requires minimal maintenance.

The following areas should be checked as required.

1. Air filters should be checked once per month. Dirty 

filters should be replaced immediately. Replacement 
filters should be available locally. Dirty and clogged 
filters will seriously effect performance of unit. 

Locate your unit in the following information to 
determine the size and quantity of filters required.

2. Blower motor and blower have permanently 

lubricated bearings that do not require any additional 
lubrication.

3. Check drain pan every six months and clean out any 

residue that may have built up.

4. Coils should be checked annually for dirt build-up 

and cleaned if necessary.

5. Re-tighten ALL electrical connections every six 

months.

IN CASE OF POWER FAILURE, EQUIPMENT MALFUNCTION

OR OTHER CIRCUMSTANCES NOT IN THE UNIT CONTROL,

THE POOL SURFACE SHOULD BE COVERED WITH A

SUITABLE COVER.

CAUTION

In the event of unit malfunction it is recommended that a
qualified service technician be notified for unit repair or

service. Danger of electrical shock and refrigerant under

pressure are present which could result in death.

MODEL

FILTER SIZE

QUANTITY

DCA500

20 x 20 x 1

1

DCA900

25 x 25 x 1

1

DCA1400

25 x 25 x 1

1

DCA2000

18 x 25 x 1

2

DCA2500

18 x 25 x 1

2

DCA3000

20 x 25 x 1

2

DCA3300

20 x 25 x 1

2

DCA3500

20 x 25 x 1

4

DCA3800

20 x 25 x 1

4

DCA4000

20 x 25 x 1

4

DCA4200

20 x 25 x 1

4

DCA5400

20 x 25 x 1

4

DCA7000

20 x 25 x 4

4

DCA8000

20 x 25 x 4

6

DCA9000

20 x 25 x 4

6

DCA110000

20 x 24 x 4

9

DCA140000

20 x 24 x 4

9

Check blower belt tension once
every six months. Turn power
supply off when inspecting belt. If
belt is found to be worn or frayed
replace with a new belt of same
size and rating. Turn power supply
on after belt has been replaced.

Содержание DCA500

Страница 1: ...I N S T A L L A T I O N O P E R A T I O N M A I N T E N A N C E SWIMMING POOL DEHUMIDIFIER OWNER S MANUAL...

Страница 2: ...ing Of Remote Condenser And Charging Instructions 7 Air Flow Balancing 8 9 Unit Start Up Procedure 10 Maintenance And Service Procedure 10 Pool Water Heating Dehumidifier Procedure 11 Pool Chemical St...

Страница 3: ...air The heat recovered by the above mentioned process known as latent heat and the electrical consumption of the compressor is delivered by the reheat condenser coil The air leaving the evaporator coi...

Страница 4: ...ool an approved drain must be provided for proper disposal If codes permit schedule 40 PVC pipe is recommended for drainage pipe Slope the condensate drain line with a minimum of 1 4 inch per foot A P...

Страница 5: ...te controls in a room that is not being conditioned by the dehumidification system unless system has remote sensors optional Controls should be mounted 5 feet from floor level on an interior wall All...

Страница 6: ...air does not short cycle back to the return inlet If dehumidifier is installed without return air duct provide a minimum of 4 feel clearance between unit and closest obstruction 3 The recommended duct...

Страница 7: ...Or Less 20 Or Less Discharge Discharge 5W Or More For Static Pressure Regain Intake TYPICAL DUCTED POOL ROOM INSTALLATION SMACNA DUCT DESIGNS DCA Dehumidifier Recommended Recommended Recommended Recom...

Страница 8: ...re that all solder joints are clean oil free and absent of any foreign material Insert copper into valve until line bottoms out in valve Complete soldering process Pressurize line set to determine if...

Страница 9: ...g Port Locations Return A L LO B HI CHART A Shows the location of the air balancing access ports and where to insert the HI and LO pressure tubes of the monometer or gauge Measure the pressure differe...

Страница 10: ...ed Under no circumstances should the unit be run for temporary heat when building construction is in progress or when there is no water in the pool HUMIDISTAT This control turns the unit on or off whe...

Страница 11: ...at to normal settings Typically between 50 RH and 60 RH and 82 F to 88 F MAINTENANCE AND SERVICE PROCEDURE Your DCA Dehumidifier requires minimal maintenance The following areas should be checked as r...

Страница 12: ...f the dehumidifier FAILURE TO FOLLOW THE ABOVE RECOMMENDATIONS WILL RESULT IN THE VOIDING OF ALL WARRANTIES FROM DCA THAT WERE EITHER EXPRESSED IMPLIED OR WRITTEN STORAGE OF POOL OR SPA WATER CHEMICAL...

Страница 13: ...Others A Air Filter B Damper Control and Timer C Outside Air Pre Heater D Bird Screen Termination 8 Mounting feet and vibratiobn isolators by others 9 Electric Gas Hot Water Add On Duct Heater By Othe...

Страница 14: ...witch in in off position automatic position Unit does not shut off Malfunctioning controls Call service technician to repair or replace control Unit not operating properly Humidistat turned off Turn h...

Страница 15: ...capacitor transformer or compressor Dehumidifying coil iced up Return air below 45 F Raise return air temperature Filters dirty or clogged Replace filters Low air flow Check blower motor and belt Adju...

Страница 16: ...Change blower rotation 3 phase only Motor going off on internal Check for rated AMP draw overload Replace motor if defective Dirty filters Replace filters Supplyandreturnairregisters Remove restrictio...

Страница 17: ...y filters Replace filters High humidity in space Incorrect duct work Check duct work design See manual Low air flow Adjust blower Check blower motor and pulley Dirty filters Replace filters Outdoor co...

Страница 18: ...be at the discretion of DCA and will be handled on a case by case basis Normally after the second compressor fails within the 3 year warranty period a problem exists in the installation maintenance o...

Страница 19: ...nusual use of supplemental heat 7 Actions or negligence of the installer or servicer of the unit that result in losses or damage of any kind including those due to inadequate A Sizing of the unit to t...

Страница 20: ...low if required must be established 6 Duct work including duct grills and diffusers must be completed 7 A thorough leak check should be performed Due to the fact that the unit may be damaged while in...

Страница 21: ...Giuffre PE Engineering 262 377 7501 tgiuffre dehumidifiercorp com Graham Gelhaar Service 262 377 7501 ggelhaar dehumidifiercorp com Jim Metzger Sales 262 377 7501 jmetzger dehumidifiercorp com Fax 26...

Отзывы: