O W N E R ’ S M A N U A L
ELECTRICAL CONNECTIONS
The DCA unit is factory pre-wired. Field wiring is limited
to power wire and the installation of wiring for 24V
controls.
Provide and install a main disconnect switch within
close vicinity of the dehumidifier. Refer to the unit
nameplate or electrical information (Following Chart) for
proper voltage, minimum ampacity and maximum main fuse
protection. All wiring and main disconnect switch should
be provided in accordance with all local, state and national
electric codes (N.E.C.).
IMPORTANT
Make sure the DCA unit is properly grounded with
correct gauge of wire via the ground lug terminal located in
the control panel. Failure to properly ground unit will void
all warranties. Supply voltage must not vary more than 10%
of the nameplate voltage while the unit is operating.
Chart A
Fuse & Ampacity Rating
The control wiring should be done according to the
wiring diagram provided with the unit. The DCA control
circuit operates at 24V.
CONTROLS, LOCATION & MOUNTING
Locate controls in an area of natural room air
circulation usually near the return air inlet. Avoid areas of
hot spots from warm air ducts, radiators or exposure to
sunlight or direct room lighting. Avoid mounting controls on
cold outside masonry walls, near door, windows or air
conditioning outlets.
Do not locate controls in a room that is not being
conditioned by the dehumidification system, unless system
has remote sensors (optional).
Controls should be mounted 5 feet from floor level on an
interior wall. All controls must be level.
MAXIMUM MINIMUM
MODEL
VOLTS
PHASE
FUSE SIZE AMPACITY
DCA500
208/2301
25 amp
19.2
DCA900/
208/230
1
30 amp
22.8
900WH
208/230
3
20 amp
14.2
460V
3
10 amp
7.0
DCA1400/ 208/230
1
40 amp
30.8
1400WH
208/230
3
25 amp
19.3
460V
3
12 amp
9.6
DCA2000/ 208/230
1
50 amp
35.6
2000WH
208/230
3
35 amp
25.6
460V
3
17.5 amp
12.4
DCA2500/ 208/230
1
70 amp
48.9
2500WH
208/230
3
40 amp
30.6
460V
3
20 amp
14.6
DCA3000/ 208/230
1
60 amp
43.6
3000WH
208/230
3
45 amp
32.4
460V
3
20 amp
15.8
DCA3300/ 208/230
3
60 amp
41.7
3300WH
208/230
3
30 amp
21.8
DCA3500/ 208/230
1
90 amp
70.9
3500WH
460V
DCA3800/ 208/230
3
70 amp
50.6
3800WH
460V
3
35 amp
25.8
DCA4000/ 208/230
1
100 amp
90.5
4000WH
460V
DCA4200/ 208/230
3
80 amp
58.6
4200WH
460V
3
40 amp
28.8
DCA5400/ 208/230
3
100 amp
73.8
5400WH
460V
3
50 amp
38.8
DCA7000
208/230
3
120 amp
83.9
7000WH
460V
3
60 amp
41.5
DCA8000
208/230
3
110 amp
92.4
8000WH
460V
3
60 amp
47.1
DCA9000/ 208/230
3
125 amp
108.5
9000WH
460V
3
70 amp
53.4
DCA11000 208/230
3
175 amp
154.0
460V
3
90 amp
77.5
575V
3
70 amp
62.7
DCA14000 208/230
3
250 amp
207.3
460V
3
125 amp
102.4
575V
3
110 amp
89.7
Floor
Approx
5 Feet
Thermostat
or Temperature Sensor
Humidistat
or Humidity Sensor
Standard 18ga. or 20ga. low voltage 24 volt wiring is required
for the controls of the dehumidifier.