21
Key Lock
When the controller is in the normal display state, the button is locked when there is no
button operation for more than 60 seconds. Press any button at this time to unlock.
4.12 Control Output
Water temperature control
•
Normal water temperature control can be performed when the controller is turned
on.
Heating and cooling:
•
When the water tank (inlet water) temperature ≤ set temperature –return difference,
heating begins. When the water tank (inlet water) temperature ≥ the set temperature,
the heating is stopped;
Cooling mode:
•
When the water tank (inlet water) temperature ≥ set tempe return difference,
the cooling starts. When the water tank (inlet water) temperature ≤ the set
temperature, the cooling stops.
Name
Remark
Code
Fluorine cycle/water cycle
heat pump
High pressure switch
Low pressure switch
Water ow switch
EEV Value
Evaporator coil sensor
Ambient temperature sensor
Absorption temperature
sensor
Exhaust temperature sensor
Inlet water temperature
(tank water temperature)
Outlet water temperature
(return water temperature)
Compressor
4-way valve
High speed fan
Low speed fan
Circulation water pump
Electric Heater
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
0=water cycle; 1=fluorine cycle
0=disconnect; 1=close
0=disconnect; 1=close
0=disconnect; 1=close
Measured value
Measured value
Measured value
Measured value
Measuredvalue
Display value=measured value + compensation
value
Display value=measured value +compensation
value
0=stop; 1=running
0=stop; 1=running
0=stop; 1=running
0=stop; 1=running
0=stop; 1=running
0=stop; 1=running