background image

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

S

W

1

S

W

2

Input type

Out B

Full scale

Zero

OFF

ON

- Input type

 

Pt100

- Option

3 wires

- Out A

4-20 mA

- Out B

0-10 V

- Full scale 

200 °C

- Zero

-50 °C

EX. of configuration

SW1 =

SW2 =

SW3 =

4

3

2

1

S

W

3

Out A

Opt

CONFIGURATION BY PC

By software DATESOFT it is possible to:
- set the default programming of the device;
- program the options not available with the dip-switch;
  (burn-out level, CJC offset, trip alarm settings, fast sampling, etc...);
- read, in real time, the input and output measures;
- follow the dip-switches configuration wizard.

To configure the device follow the next steps:
1) Power-on the device.
2) Open the protection plastic label on the front of the device. 
3) Connect the interface PRODAT to the PC (COM port)
    and to the device (PGRM connector).
4) Open DATESOFT.
5) Select the COM port in use.
6) Click on “Open COM”.
7) Click on the icon “Program”.
8) Set the programming data.
9) Click on the icon “Write” to send the programming data to the device.

Warning: during these operations the device must always be powered and the TX/RX cable always connected.
For information about DATESOFT refer to the software's user guide.

J

1

TX/RX CABLE

PRODAT

COM PORT

P.C.

V+ V-

U

V

PGRM

Plastic label protection

DAT

POWER SUPPLY

UNIT

PROGRAMMING

CONFIGURATION BY DIP-SWITCHES

1) Open the suitable door on the side of the device. 

2) Set the input type by the dip-switch SW1 [1..5] (see TAB.1)

3) Set the output A type by the dip-switch SW1 [7..8] and SW2 [1..2]  (see TAB.2)

4) Set, if available, the input option by the dip-switch SW1 [6] (see TAB.3)

5) Set the minimum input scale value (Zero)  by the dip-switch SW3 [1..4] (see TAB.4)*

6) Set the maximum input value (Full scale) by the dip-switch SW2 [3..8] (see TAB.4)*

NOTE:
-  It  is  also  possible  to  set  the  dip-switches  using  the  wizard  of  the 
configuration  software  following  the  procedure  described  in  the  section 
”Configuration by PC” until the step 6 and clicking on icon “Switch”.

THRESHOLD OPERATION

For the high alarm the relay goes on when the input signal is higher than 
the  trip  level  and  after  the  delay  time.  The  relay  goes  off  only  when  the 
input signal is lower than the trip level minus the hysteresis value or when 
reaches the minimum value of the input scale and after the delay time.

For the low alarm the relay goes on when the input signal is lower than the 
trip level  and after the delay time. The relay goes  off only when the input 
signal  is  higher  than  the  trip  level  plus  the  hysteresis  value  or  when 
reaches the maximum value of the input scale and after the delay time.

T(delay)

T(delay)

Active relay

Trip level

Trip level - hyst.

T(delay)

T(delay)

Active relay

Trip level 

Trip level + hyst.

HIGH ALARM THRESHOLD

LOW ALARM THRESHOLD

Содержание DAT 4530

Страница 1: ...ure of 12 5 mm thickness suitable for DIN rail mounting in compliance with EN 50022 and EN 50035 standards USER INSTRUCTIONS The connections must be made as shown in the section Connections It is possible to configure the converter on field by dip switch or Personal Computer as shown in the section Programming The configuration by dip switches can be made also if the device is powered note after t...

Страница 2: ...MMING CONFIGURATION BY DIP SWITCHES 1 Open the suitable door on the side of the device 2 Set the input type by the dip switch SW1 1 5 see TAB 1 3 Set the output A type by the dip switch SW1 7 8 and SW2 1 2 see TAB 2 4 Set if available the input option by the dip switch SW1 6 see TAB 3 5 Set the minimum input scale value Zero by the dip switch SW3 1 4 see TAB 4 6 Set the maximum input value Full sc...

Страница 3: ... V 0 20 mA SW2 2 1 4 20 mA 0 10 V 0 5 V Out B NOTES To set the input range refer to the TAB 4 next pages referred to the input type selected by the TAB 1 If the dip switches SW1 1 5 are all set in the position 0 EPROM the device will follow the configuration programmed by PC input type and range output type and range trip alarm s settings and options If the dip switches SW2 3 8 and SW3 1 4 are all...

Страница 4: ... W Full Scale SW2 6 5 4 3 Default 50 55 60 65 70 75 80 85 90 95 100 110 115 120 W 7 8 SW2 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 SW2 220 230 240 250 260 270 280 290 300 310 320 330 340 350 SW2 380 390 400 410 420 430 440 450 460 470 500 500 30 20 200 360 480 490 500 370 210 105 W W W 6 5 4 3 7 8 6 5 4 3 7 8 6 5 4 3 7 8 TAB 4d Resistance 500 ohm input scale settings Zero SW3 4 ...

Страница 5: ...0 20 2 5 2 11 25 15 5 20 20 20 16 11 5 mA mA mA mA mA 6 5 4 3 7 8 6 5 4 3 7 8 TAB 4f Current input scale settings Zero SW3 4 3 2 1 Default 0 1 5 3 3 5 4 4 5 5 5 5 6 6 5 7 7 5 8 Volt Full Scale SW2 6 5 4 3 Default 0 5 0 6 0 8 1 1 2 1 4 1 6 1 8 2 2 2 2 4 2 6 2 8 3 3 2 Volt 7 8 SW2 3 4 3 6 3 8 4 4 2 4 4 4 6 4 8 5 5 2 5 4 5 6 5 8 6 6 2 Volt SW2 6 8 7 7 2 7 4 7 6 7 8 8 8 2 8 4 8 6 8 8 9 9 2 9 4 Volt SW...

Страница 6: ...nal cables motors induction ovens inverters etc and to use shielded cable for connecting signals LIGHT SIGNALLING LED COLOUR STATE DESCRIPTION PWR GREEN ON OFF Device powered Device not powered BLINKING Wrong dip switches settings ALARM RED ON OFF Trip alarm active Trip alarm not active DAT 4530 Pt100 0 200 C 4 20 mA 4 20 mA 3wires Input type Input scale Out A scale Options Out B scale HOW TO ORDE...

Отзывы: