Datexel reserves its rights to modify totally or in part the characteristics of its products without notice at any time 

.

ED.02.15-R.01

DIMENSIONS (mm)

90

112

P

G

R

M

12,5

INSTALLATION INSTRUCTIONS

The device is suitable for fitting to DIN rails in the vertical position.
For optimum operation and long life follow these instructions:

When the devices are installed side by side it may be necessary to 
separate them by at least 5 mm in the following cases:

- If panel temperature exceeds 45°C.
- Use of high power supply value ( > 27 Vdc ).
- Use of one or both current outputs.
- Use of active current input.

Make  sure  that  sufficient  air  flow  is  provided  for  the  device  avoiding  to 
place raceways or other objects which could obstruct the ventilation slits. 
Moreover  it  is  suggested  to  avoid  that  devices  are  mounted  above 
appliances generating heat; their ideal place should be in the lower part 
of the panel.
Install the device in a place without vibrations.
Moreover  it  is  suggested to  avoid routing  conductors  near  power signal 
cables  (motors,  induction  ovens,  inverters  etc...)  and  to  use  shielded 
cable for connecting signals.

LIGHT SIGNALLING

LED

 

COLOUR

 

STATE

 

DESCRIPTION

PWR 

GREEN 

ON 

OFF

Device powered 

Device not powered

BLINKING

Wrong dip-switches settings

ALARM

RED

ON 

OFF

Trip alarm active

Trip alarm not active

DAT 4530   / Pt100 / 0 ÷ 200 °C / 4 ÷ 20 mA / 4 ÷ 20 mA / 3wires

Input type

Input scale

Out A scale

Options

Out B scale

HOW TO ORDER

The device is provided as requested on the Customer's order.
Refer to the section “Programming” to determine the input and output ranges. 
In case of the configuration is not specified, the parameters must be set by the user.

ORDER CODE EXAMPLE: 

POWER SUPPLY

OUTPUT A

OUTPUT B

INPUT

ISOLATION STRUCTURE

TRIP 

ALARM

CONNECTIONS

POWER SUPPLY(*)

INPUT SIDE

OUTPUT SIDE

I

G

RTD/RES 2W

I

H

G

RTD/RES 3W

+

-

Vdc

U

V

L

I

+

TC

mV 

+

E

C

+

-

D

F

+

-

TX

I

H

G

Pot

R

lo

a

d

+

S

T

V

Vout

CHANNEL B

R

lo

a

d

+

Q

R

Iout

mA

Rload

+

R

T

Iout

+

Vdc

R

lo

a

d

+

O

P

V

Vout

CHANNEL A

R

lo

a

d

+

M

N

Iout

mA

Rload

+

N

P

Iout

+

TRIP ALARM

A

B

I

H

G

RTD/RES 4W

L

F

C

+

-

Passive mA input

Connected to active

 current loop

Active mA input

Connected to passive

 current loop

(*) Note: for UL installation the 

device must be powered using a 

power supply unit classified 

NEC class 2 or SELV

Содержание DAT 4530

Страница 1: ...ure of 12 5 mm thickness suitable for DIN rail mounting in compliance with EN 50022 and EN 50035 standards USER INSTRUCTIONS The connections must be made as shown in the section Connections It is possible to configure the converter on field by dip switch or Personal Computer as shown in the section Programming The configuration by dip switches can be made also if the device is powered note after t...

Страница 2: ...MMING CONFIGURATION BY DIP SWITCHES 1 Open the suitable door on the side of the device 2 Set the input type by the dip switch SW1 1 5 see TAB 1 3 Set the output A type by the dip switch SW1 7 8 and SW2 1 2 see TAB 2 4 Set if available the input option by the dip switch SW1 6 see TAB 3 5 Set the minimum input scale value Zero by the dip switch SW3 1 4 see TAB 4 6 Set the maximum input value Full sc...

Страница 3: ... V 0 20 mA SW2 2 1 4 20 mA 0 10 V 0 5 V Out B NOTES To set the input range refer to the TAB 4 next pages referred to the input type selected by the TAB 1 If the dip switches SW1 1 5 are all set in the position 0 EPROM the device will follow the configuration programmed by PC input type and range output type and range trip alarm s settings and options If the dip switches SW2 3 8 and SW3 1 4 are all...

Страница 4: ... W Full Scale SW2 6 5 4 3 Default 50 55 60 65 70 75 80 85 90 95 100 110 115 120 W 7 8 SW2 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 SW2 220 230 240 250 260 270 280 290 300 310 320 330 340 350 SW2 380 390 400 410 420 430 440 450 460 470 500 500 30 20 200 360 480 490 500 370 210 105 W W W 6 5 4 3 7 8 6 5 4 3 7 8 6 5 4 3 7 8 TAB 4d Resistance 500 ohm input scale settings Zero SW3 4 ...

Страница 5: ...0 20 2 5 2 11 25 15 5 20 20 20 16 11 5 mA mA mA mA mA 6 5 4 3 7 8 6 5 4 3 7 8 TAB 4f Current input scale settings Zero SW3 4 3 2 1 Default 0 1 5 3 3 5 4 4 5 5 5 5 6 6 5 7 7 5 8 Volt Full Scale SW2 6 5 4 3 Default 0 5 0 6 0 8 1 1 2 1 4 1 6 1 8 2 2 2 2 4 2 6 2 8 3 3 2 Volt 7 8 SW2 3 4 3 6 3 8 4 4 2 4 4 4 6 4 8 5 5 2 5 4 5 6 5 8 6 6 2 Volt SW2 6 8 7 7 2 7 4 7 6 7 8 8 8 2 8 4 8 6 8 8 9 9 2 9 4 Volt SW...

Страница 6: ...nal cables motors induction ovens inverters etc and to use shielded cable for connecting signals LIGHT SIGNALLING LED COLOUR STATE DESCRIPTION PWR GREEN ON OFF Device powered Device not powered BLINKING Wrong dip switches settings ALARM RED ON OFF Trip alarm active Trip alarm not active DAT 4530 Pt100 0 200 C 4 20 mA 4 20 mA 3wires Input type Input scale Out A scale Options Out B scale HOW TO ORDE...

Отзывы: