Datexel reserves its rights to modify totally or in part the characteristics of its products without notice at any time
.
ED.02.15-R.01
DIMENSIONS (mm)
90
112
P
G
R
M
12,5
INSTALLATION INSTRUCTIONS
The device is suitable for fitting to DIN rails in the vertical position.
For optimum operation and long life follow these instructions:
When the devices are installed side by side it may be necessary to
separate them by at least 5 mm in the following cases:
- If panel temperature exceeds 45°C.
- Use of high power supply value ( > 27 Vdc ).
- Use of one or both current outputs.
- Use of active current input.
Make sure that sufficient air flow is provided for the device avoiding to
place raceways or other objects which could obstruct the ventilation slits.
Moreover it is suggested to avoid that devices are mounted above
appliances generating heat; their ideal place should be in the lower part
of the panel.
Install the device in a place without vibrations.
Moreover it is suggested to avoid routing conductors near power signal
cables (motors, induction ovens, inverters etc...) and to use shielded
cable for connecting signals.
LIGHT SIGNALLING
LED
COLOUR
STATE
DESCRIPTION
PWR
GREEN
ON
OFF
Device powered
Device not powered
BLINKING
Wrong dip-switches settings
ALARM
RED
ON
OFF
Trip alarm active
Trip alarm not active
DAT 4530 / Pt100 / 0 ÷ 200 °C / 4 ÷ 20 mA / 4 ÷ 20 mA / 3wires
Input type
Input scale
Out A scale
Options
Out B scale
HOW TO ORDER
The device is provided as requested on the Customer's order.
Refer to the section “Programming” to determine the input and output ranges.
In case of the configuration is not specified, the parameters must be set by the user.
ORDER CODE EXAMPLE:
POWER SUPPLY
OUTPUT A
OUTPUT B
INPUT
ISOLATION STRUCTURE
TRIP
ALARM
CONNECTIONS
POWER SUPPLY(*)
INPUT SIDE
OUTPUT SIDE
I
G
RTD/RES 2W
I
H
G
RTD/RES 3W
+
-
Vdc
U
V
L
I
+
TC
mV
+
E
C
V
+
-
D
F
+
-
TX
I
H
G
Pot
R
lo
a
d
+
S
T
V
Vout
CHANNEL B
R
lo
a
d
+
Q
R
Iout
mA
Rload
+
R
T
Iout
+
Vdc
R
lo
a
d
+
O
P
V
Vout
CHANNEL A
R
lo
a
d
+
M
N
Iout
mA
Rload
+
N
P
Iout
+
TRIP ALARM
A
B
I
H
G
RTD/RES 4W
L
F
C
+
-
Passive mA input
Connected to active
current loop
Active mA input
Connected to passive
current loop
(*) Note: for UL installation the
device must be powered using a
power supply unit classified
NEC class 2 or SELV