SE4-PLUS Series
Instruction Manual
13
2.2.2. Safety distance variation with Blanking function activated
The activation of the
Floating Blanking
function generates a
resolution reduction of the device.
Consequent to this reduction, signalled also by the device
signalling lamp (
see section 6.6 “Blanking function”)
, the light
curtain has to be repositioned at the right safety distance
according to the indications supplied in the previous section and
complying with the real device resolution.
The folllowing table summarises the resolution variation in all
possibile applications:
Real resolution with Floating Blanking
Declared
resolution
1 beam
2 beams
3 beams
14 mm
21 mm
28 mm
35 mm
30 mm
48 mm
66 mm
84 mm