DKG-209 User Manual V-29
(20.08.2013)
- 7 -
Term Function
Technical data
Description
18
OIL PRESSURE SENDER
Input, 0-5000 ohms
Analogue oil pressure sender connection. Do
not connect the sender to other devices. The
input has programmable characteristics and
connects to any kind of sender.
19
COOLANT TEMP. SENDER
Input, 0-5000 ohms
Analogue
high
temperature
sender
connection. Do not connect the sender to
other devices. The input has programmable
characteristics and connects to any kind of
sender.
20
CURR_COMMON
Current
transformer
inputs, 5A-AC
Connect the generator current transformer
terminals to these inputs. Do not connect the
same current transformer to other instruments
otherwise a unit fault will occur. Connect each
terminal of the transformer
to the unit’s related
terminal. Do not use grounding. Correct
polarity of connection is vital. If the measured
power is negative, then change the polarity of
each 3 current transformers. The rating of the
transformers should be the same for each of
the 3 phases. The secondary winding rating
shall be 5 Amperes. (For ex. 200/5 Amps).
21
CURR_1
22
CURR_2
23
CURR_3
24
LOW OIL PRESSURE
Digital inputs
These
inputs
have
programmable
characteristics selected via the program
menu. Each input may be driven by a
‘normally closed’ or ‘normally open’ contact,
switching either or battery-. The effect
of the switch is also selectable from a list. See
PROGRAMMING section for more details.
25
HIGH TEMP
26
EMERGENCY STOP
27
FUEL LEVEL
28
SPARE-1