DKG-209 User Manual V-29
(20.08.2013)
- 44 -
Program Group: Input Configuration (Spare-1 Input)
(password level-2)
Parameter Definition
Unit
Fac.Set Description
Action
2
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
Latching
0
0:
Non latching
1:
Latching
Contact type
0
0:
Normally open
1:
Normally closed
Switching
0
0:
Battery negative
1:
Battery positive
Response delay
0
0:
No delay
1:
Delayed (4sec)
The parameters below define the functions of relay outputs. The unit has 5 relay outputs. The fixed
function relays are Fuel, Start, Mains Contactor and Generator Contactor. ALARM RELAY has
programmable functions, selected from a list.
Program Group: Relay Definitions (password level-2)
Parameter Definition
Unit Fac.Set Description
Relay 01 Definition
3
RELAY-1 function selected from list