Program Group: Controller Configuration
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(1)
LCD Contrast
-
35
This parameter is used to set LCD contrast. Adjust
for the best viewing angle.
(2)
Language Selection
-
0
0:
English language selected.
1:
Turkish language selected. This language may
depend on the country where the unit is intended to
be used.
2:
Chinese language selected
3:
The unit will ask for manual language selection at
power-on.
(2)
Secondary Volt/Freq
-
0
0:
Use primary voltage/frequency limits
1:
Use secondary voltage/frequency limits
(2)
Single phase Enable
-
0
0:
3-phase system
1:
Single phase system
(2)
Line-to-Line Voltages
-
0
0:
Display Line to Neutral voltages as default
1:
Display Line to Line voltages as default
(1)
Genset Default Display
-
0
This parameter selects the screen which is displayed
during genset on load operation.
0:
screen 3 (or 4) electrical, large characters
1:
screen 5 engine parameters, large characters
2:
screen 6 (or 7) maximum information, small
characters
3:
screen 8 (or 9)
Details of each screen are explained in chapter 3.2
(2)
Fault Holdoff Timer
sec
12
This parameter defines the delay after the engine
runs and before the fault monitoring is enabled.
(1)
Alarm Relay Timer
sec
60
This is the period during which the
ALARM
relay is
active. If the period is set to 0, this will mean that the
period is unlimited.
(1)
Intermittent Alarm Relay
-
0
0:
continuous
1:
intermittent (turns on and off every second)
(2)
Charge Alternator
Shutdown
-
1
0:
The charge input generates
CHARGE FAIL
warning, and does not stop the engine.
1:
The charge input generates
CHARGE FAIL
alarm,
and stops the engine.
(1)
Emergency Backup
Operation
-
0
0:
In TEST mode, the load will not be transferred to
the genset even if the mains fail.
1:
In TEST mode, the load will be transferred to the
genset if the mains fail.
(2)
Enable Delayed Simulate
Mains
-
0
0:
Delayed simulate mains not enabled
1:
Delayed simulate mains enabled
(2)
Modem Enable
-
0
0:
No modem connection, the serial port is connected
to PC
1:
Modem connected.
(2)
SMS Enable
-
0
0:
SMS not enabled
1:
SMS enabled
(2)
MODBUS Address
-
0
0:
RAINBOW communication protocol.
1-144:
MODBUS communication. This parameter is
also the MODBUS controller address of the unit.
(1)
Oil Pressure in psi
-
0
0:
oil pressure display in bars
1:
oil pressure display in psi
(1)
Temperature in °F
-
0
0:
temperature display in degrees C
1:
temperature display in degrees F