D-700 MK3 User Manual Firmware V-16.8
- 93 -
The AUTO mode is entered by pressing the
button.
The AUTO mode is used for the automatic operation of the genset system.
▪
AMF Mode:
The controller will constantly monitor the mains availability. It will run the engine and
transfer the load when a mains failure occurs.
▪
Synchronizing & Load Sharing Mode:
The controller will monitor the
REMOTE STAR
T signal.
When the signal arrives, it will run the genset, synchronize to the busbar, get in parallel, ramp up and
start sharing the load. Depending on settings, the controller may decide to stop the genset, or restart
it anytime in order to achieve the necessary available power on the busbar.
▪
ATS Mode:
The controller will constantly monitor the mains availability. When a mains failure occurs,
it will activate its REMOTE START output, thus the genset group will run and the controller will
transfer the load. When the mains is back again, it will open the genset contactor and it will close the
mains contactor.
The mains availability evaluation sequence is below:
•
If at least one of the mains phase voltages or the mains frequency is outside limits, the mains will be
supposed failing. Otherwise mains is available.
•
If a Simulate Mains signal is present, then mains are made available
•
If a Force to Start signal is present, then mains are unavailable
•
If a Remote Start input is defined, then this signal decides of mains availability.
When mains are evaluated as “unavailable” then an engine start sequence begins:
•
The unit waits during
Engine Start Delay
for skipping short mains failures. If the mains is restored
before the end of this timer, the genset will not start.
•
The unit turns on the fuel and preheat glow plugs (if any) and waits for
preheat timer
.
•
The engine will be cranked for programmed times during crank timer. When the engine fires, the
crank relay will be immediately deactivated. See section
Crank Cutting
for more details.
•
The engine will run at idle speed during Idle Speed Timer.
•
The engine will run unloaded during engine heating timer.
•
If alternator phase voltages, frequency and phase order are correct, the unit will wait for the
generator contactor period and the generator contactor will be energized.
If a panel lock input is defined and signal is applied, then mode
change with pushbuttons will not occur. However, display
navigation buttons are still enabled and parameters may be
visualized.
14.3. AUTO MODE
Содержание D-700 MK3
Страница 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Страница 51: ...D 700 MK3 User Manual Firmware V 16 8 51 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 53: ...D 700 MK3 User Manual Firmware V 16 8 53 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3...
Страница 63: ...D 700 MK3 User Manual Firmware V 16 8 63 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS...
Страница 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Страница 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Страница 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Страница 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Страница 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Страница 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Страница 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Страница 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...
Страница 83: ...D 700 MK3 User Manual Firmware V 16 8 83...