D-700 MK3 User Manual Firmware V-16.8
- 112 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
E-mail on IP Change
-
0
1
0
This parameter controls e-mail sending
when IP address of GPRS or ethernet
connection is changed. No warnings
generated.
0:
no e-mail on IP change
1:
e-mail sent on IP change
Fuel Pump Low Limit
%
0
100
20
If the fuel level measured from the
sender input falls below this level, then
the FUEL PUMP function will become
active.
Fuel Pump High Limit
%
0
100
80
If the fuel level measured from the
sender input goes above this level, then
the FUEL PUMP function will become
passive.
Warning Before Start
-
0
1
1
This parameter controls the activation of
the ALARM output
during “Engine Start
Delay” timer before engine run.
0:
no warning before start
1:
warning before start
Latch all Warnings
-
0
1
0
0:
warnings are latching/non-latching on
parameter control
1:
all warnings are latched. Even if the
fault source is removed, warnings will
persist until manually reset.
Remote Control Enable
-
0
1
1
This parameter controls remote control
of the unit through Rainbow, Modbus
and Modbus TCP/IP.
0:
remote control disabled
1:
remote control enabled
Annunciator Mode
-
0
1
0
0:
normal operation
1:
the unit becomes an annunciator of
the remote unit. Engine/genset control
functions are disabled.
CT Location
-
Genset
Load
Genset
0:
CTs are at the genset side. Mains
currents are not measured.
1:
CTs are at load side. Both mains and
genset currents are monitored following
contactor status.
Reverse CT Direction
-
0
1
0
This parameter is useful to invert all CT
polarities at the same time.
0:
normal CT polarity assumed.
1:
reverse CT polarity assumed.
Buzzer Enable
-
0
1
0
Internal buzzer control
0: buzzer disabled
1: buzzer enabled
Log Record Period
sec
5
3600
5
This parameter adjusts the data logging
frequency to micro-SD or USB Flash
memories. Frequent recording will
require more memory capacity.
With a period of 2 seconds, 4GB per
year of memory is necessary.
With a period of 1 minute, 133MB is
consumed per year.
17.1. CONTROLLER CONFIGURATION GROUP (continued)
Содержание D-700 MK3
Страница 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Страница 51: ...D 700 MK3 User Manual Firmware V 16 8 51 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 53: ...D 700 MK3 User Manual Firmware V 16 8 53 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3...
Страница 63: ...D 700 MK3 User Manual Firmware V 16 8 63 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS...
Страница 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Страница 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Страница 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Страница 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Страница 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Страница 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Страница 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Страница 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...
Страница 83: ...D 700 MK3 User Manual Firmware V 16 8 83...