AIR-COOLED FLUID COOLER
24
•
Air-Cooled Condenser Manual
5.0
CONTROLS
5.1
Electronically Commutated (EC) Axial Fan Motors (Optional)
Fluid coolers with Electronically Commutated (EC) axial fan motor(s) will modulate the fan
motor(s) from minimum speed (approximately 20%) to full fan speed (i.e., throttling range
–
proportional band) by means of an electronic proportional fluid temperature sensing controller.
All fan motor(s) are modulated equally over the throttling range. The fluid temperature sensing
element of the controller is strapped to the leaving fluid header.
The fluid temperature sensing controller is typically set to start the fan(s) and run at a minimum
speed (approximately 20%) when the leaving fluid temperature reaches 85°F (29.4°C). The
controller will increasingly modulate the fan speed until full speed is reached at approximately
95°F (35°C) fluid temperature. This is generally the desired range for glycol cooled systems.
This setpoint is factory set but will require field adjustment based on local conditions and
application.
5.2
Permanent-Split Capacitor (PSC) Type Fan Motors
Fluid coolers with Permanent-Split Capacitor (PSC) fan motors are cycled on and off by
individual fluid-sensing thermostats on all fan motor(s) except the first fan. The lead or first
fan motor (closest to the electrical enclosure) will run continuously whenever there is a call for
cooling via an auxiliary signal sent from the indoor evaporator section. The thermostat sensing
bulbs are strapped to the leaving fluid header.
The fluid-sensing thermostats have adjustable setpoints which are staggered to maintain fluid
temperature in the 85°F to 105°F (29.4°C to 40.6°C) range. This is generally the desired
range for glycol cooled systems. These setpoints are factory set but will require field
adjustment based on local conditions and application. See
BULB MOUNTING INSTRUCTIONS10.0
for factory default thermostat setpoints.
On units with an optional Energy Saver (free cooling) coil the lead or first fan motor (closest
to the electrical enclosure) will be controlled by a thermostat. See section 4.3 below for more
detail.
5.3
Energy Saver Cooling (Optional)
In colder climates, the evaporator will often be equipped with an optional free cooling coil to
take advantage of the colder ambient temperatures. When incoming fluid falls below the
setpoint programmed through the unit
’s dap4 microprocessor controller, factory default is 50°F
(10°C), the Energy Saver becomes available.
On older units with the DAP-II control, the evaporator will have an adjustable fluid-sensing
thermostat that is factory default set at 50°F (10°C), to control when the Energy Saver
becomes available.
5.3.1 Systems with EC Fan Motor(s)
Systems with EC fan motor(s) and the optional Energy Saver coil will start and run all fan
motor(s) at a setpoint to take advantage of the colder ambient temperatures. The factory
Содержание DAFC 06
Страница 1: ...1 Air Cooled Condenser Manual ...
Страница 40: ...AIR COOLED FLUID COOLER 40 Air Cooled Condenser Manual Figure 6 Fluid Temperature Sensor Bulbs ...
Страница 42: ...AIR COOLED FLUID COOLER 42 Air Cooled Condenser Manual Figure 8 Fully Insulated Bulbs ...
Страница 44: ...NOTES 44 Air Cooled Condenser Manual ...
Страница 45: ...Publication Fluid Cooler IOM FluidCoolerIOM 03 2022 docx Date 03 2022 ...