AIR-COOLED FLUID COOLER
19
•
Air-Cooled Condenser Manual
either visible or concealed before installation.
•
Use correctly sized copper wire only and verify that all electrical connections are
tight before turning power “ON”.
•
Check all electrical connections periodically and tighten as necessary.
•
All field supplied signal cable (if applicable) shall have the following specifications
(Control wires only):
a. Conductors
—AWG stranded copper
b. Twisted pair (minimum eight twists per foot)
c. Braided shield or foil shield
d. UL approved temperature rated to 105°C
e. UL approved voltage rated to 600V
f. UV-resistant, oil resistant and moisture-resistant if not provided in conduit.
g. Plenum rated (As required by national or local codes.)
•
All field supplied wires shall have the following guidelines:
a. Conductors - stranded copper and sized per circuit ampacity under NEC
b. UL approved temperature rated to 105°C
c. UL approved voltage rated to 600V
d. UV-resistant, oil resistant and moisture-resistant if not provided in conduit.
e. Wire Ampacity: Please refer to NEC for other wire sizes
4.2
Electrical Service
Before proceeding with the electrical connections, make certain that the volts, hertz, and
phase correspond to that specified on the unit electrical nameplate. Check to be sure the
electrical service provided by the utility company is enough to handle the additional load
imposed by this equipment.
Remote fluid coolers will typically require one power source. Glycol systems with fluid coolers
and loose pump(s) typically require one power source for the fluid cooler and will require one
additional source for a single pump or two additional sources for dual pumps. Systems where
the pump(s) are mounted and piped integral to the fluid cooler will usually require a single
power source.
4.3
Nameplate Ratings
Refer to the unit electrical nameplate for equipment electrical requirements. The unit
nameplate is located inside the electrical control enclosure door. The nameplate includes
Minimum Circuit Ampacity (MCA) also known as wire sizing amps which indicates the
minimum required wire gauge. The Maximum Overcurrent Protection (MOP) device amps
indicates the maximum circuit breaker or fuse size required to protect the system. Max. Fuse
or Max. CKT. BKR. indicates the maximum breaker or fuse size and this information is used
to size the appropriate fuses or a Heating, Air Conditioning, and Refrigeration (HACR) type
circuit breaker. Other protection devices are not allowed based upon the product UL listing.
The facility main distribution panel which provides electrical service to the Data Aire equipment
Содержание DAFC 06
Страница 1: ...1 Air Cooled Condenser Manual ...
Страница 40: ...AIR COOLED FLUID COOLER 40 Air Cooled Condenser Manual Figure 6 Fluid Temperature Sensor Bulbs ...
Страница 42: ...AIR COOLED FLUID COOLER 42 Air Cooled Condenser Manual Figure 8 Fully Insulated Bulbs ...
Страница 44: ...NOTES 44 Air Cooled Condenser Manual ...
Страница 45: ...Publication Fluid Cooler IOM FluidCoolerIOM 03 2022 docx Date 03 2022 ...