![Data Aire DAFC 06 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/data-aire/dafc-06/dafc-06_installation-operating-and-maintenance-manual_511079014.webp)
AIR-COOLED FLUID COOLER
14
•
Air-Cooled Condenser Manual
Figure 3 Typical Fluid Cooler System
NOTES:
1. - - - - - - - Indicates Field Piping - Provided by the installing contractor.
2. The expansion tank is a required component of a proper system installation. The tank
can be provided by Data Aire as an option.
3. All water/glycol field piping must be designed and installed in accordance with ASHRAE
standards and local codes.
4. Centrifugal pumps and components are optional. A flow switch is required with dual
pump application.
5. Variable pump flow control or a bypass system are the responsibility of the installing
contractor when a 2-way valve is specified in the evaporator section of a water/glycol
cooled unit.