Output
overcurrent
InsLine x
OC,
AvgLine x
OC
If output of the
inverter is in over-
current state
Contact the service center.
7
PWM
FAULT
Line x OC2,
x UVLO
Inverter internal fault
Contact the service center.
8
Relay
FAULT
Relay_Open
Relay-Short
Relay fuse and failure Contact the service center.
9
Communication
FAULT
Comm. Error
MMI communication
fault
Contact the service center.
10
Temperature
FAULT
Over Heat1
Over-temperature
failure
Contact the service center.
11
Output current
FAULT
Balance
Current
Output current
imbalance
Contact the service center.
12
HARDWARE
FAULT
Hardware
OC
Output over-current
Contact the service center.
13
INSULATION
FAULT
PV
Insulation
Insufficient insulation
resistance
Contact the service center.
14
HARDWARE
OH
Over Heat2
Hardware overheat
Contact the service center.
15
RCMU
FAULT
Residual
OC
Leakage current is
over the standard
value
Contact the service center.
16
Grid
Overvoltage
InsLine xx
OV,
AvgLine xx
OV
If the grid voltage
exceeds the set
voltage
Contact the installation company and then call
the service center.
17
Grid
Undervoltage
AvgLine xx
UV
If the grid voltage is
below the set voltage
Contact the installation company and then call
the service center.
18
Grid
Frequency fault
Over
Frequency,
Under
Frequency
Grid frequency fault
Contact the installation company and then call
the service center.
19
Output DC
detection
x DC
Current
DC output is
introduced to
the grid
Contact the service center.