Battery Charging Requirements 

The default charging parameters are shown below. Use this as a reference to make sure the battery selected is compatible with 
the inverter. It is recommended that you use a deep cycle battery when the mode of operation is not set as one of the two back-
up modes. 

PARAMETERS 

LEAD-ACID BATTERY (DEFAULT VALUES) 

LITHIUM BATTERIES (DEFAULT VALUES) 

Max. Current 

60A 

60A 

Float Voltage 

54.4Vdc 

N/A 

Bulk Voltage 

56.4Vdc 

Darfon B05LM LMNC: 57.4Vdc 
Panasonic DCB-105ZK LMNC : 52Vdc 
Darfon B10LF/B12LF LFP: 54.75Vdc 
Darfon B09ULF/B14ULF LFP: 51.5Vdc 

Charging 
process 

First - charging voltage increases to 56.4V. 
Second- charging voltage will maintain at 56.4V until charging 
current is down to 2A. 
Third- goes to float voltage at 54.4V. 

First – SOC voltage increases to bulk voltage. 
Second - charging voltage will maintain until SOC is 99%. 
Third- stop charging after 1 hour. 

 

 

 

 

Communication Ports 

The inverter has communication ports for data logger communication, battery communication, external display connection and 
parallel operation. The ports are located inside the distribution box, 

on the top bulkhead panel. 

 

 

 

PORT 

FUNCTION 

RJ45 

For External Display. The inverter can only connect to external displays provided by Darfon.   

RJ12 (x2) 

For Parallel (Stacking) Function. Only inverters of the same model can be installed in parallel. 

RS485 S 

For Data Logger. Check Darfon website for compatible data logger models. 

Dip 
Switches 

For Long Distance RS485 Communication. If the distance between the Data Logger and Hybrid inverter is greater than 50m, 
then the termination resistor switch on the Hybrid should be switched ON. If the distance between the Data Logger and 
Hybrid is less than 50m, then the termination resistor switch on Hybrid should be switched OFF. 

RS485 M 

For Battery BMS. The inverter can only communicate with lithium batteries listed in the “Battery Charging Requirements” 
section. If installing with Lead Acid or other lithium batteries not listed, the inverter will not be able to communicate with the 
battery and the battery type should be set as Lead Acid. 

 

 

Bulk Voltage

Bulk

Absorption

Float

Voltage

  Current

Time

Float Voltage

Bulk Voltage

Bulk

Absorption

Voltage

  Current

Time

Содержание H5001

Страница 1: ...INSTALLATION MANUAL H5001 HYBRID INVERTER...

Страница 2: ...rs 8 Battery Charging Requirements 9 Communication Ports 9 Access Panel 10 TURNING THE SYSTEM ON OFF 11 Turning On the System 11 Turning Off the System 11 OPERATION AND DISPLAY PANEL 12 Display Overvi...

Страница 3: ...enance or cleaning or working on any circuits connected to the inverter Turning off controls will not reduce this risk Internal capacitors can remain charged for 5 minutes after disconnecting all sour...

Страница 4: ...UNCTION Piston Breakers For Over Current Protection of Grid L1 L2 Dip Switches For Firmware Update Jumpers For Firmware Update USB B For Computer Connection Communication Ports Power Switch Battery Br...

Страница 5: ...ution Degree rating The unit is for indoor applications only and must be mounted in a protected area that is dry free of excessive dust and has adequate air flow CAUTION The inverter is heavy 87lb 40k...

Страница 6: ...d 5 Time Of Use Low electricity cost Operate as Back up mode High electricity cost Operate as Residential mode 6 Time Of Use With Battery Feed In Low electricity cost Operate as Back up mode High elec...

Страница 7: ...se power surges that exceeds the inverter specifications When the grid is present the inverter can accept power surges up to 7 5kW for 30 seconds When the grid is absent the inverter can accept power...

Страница 8: ...ng or modifying any connections To prevent the risk of electric shock make sure the ground wire is properly earthed before operating this unit whether the grid is connected or not To reduce the risk o...

Страница 9: ...communication battery communication external display connection and parallel operation The ports are located inside the distribution box on the top bulkhead panel PORT FUNCTION RJ45 For External Displ...

Страница 10: ...r Over Current Protection There are three circuit breakers that protect the Grid path One circuit breaker is in the distribution box and is rated at 40A The piston breakers are for Grid L1 L2 and are...

Страница 11: ...e battery Refer to the battery s instruction manual Turn on the grid breaker if grid is connected Turn on the Power Switch Wait for system bootup and the fans to turn on plus 3 beeps Turn on the Load...

Страница 12: ...ction Exits setting mode Previous page previous item or decrease number ICON DESCRIPTION Represents the PV Array Represents the Battery Pack Represents the Utility Represents the Load Represents the H...

Страница 13: ...d use the key to set it When done press the key You will see a message stating the settings are being updated When you see Setting OK message press any key Manually restart the inverter using the Powe...

Страница 14: ...AC breakers must be sized for 40A or less and 2 all wiring must be sized for 40A or more The following diagram shows how the distribution box is electrically connected to the hybrid inverter NOTES Th...

Страница 15: ...If the error remains turn off the Utility and the inverter s Grid breaker Then measure the Grid and make sure the impedance of L1 L2 and N relative to ground and to each other should be an open circui...

Страница 16: ...the Grid or PV to charge the battery Warning code will change to 62 once the battery voltage is above 44V or the SOC is above 10 Note Battery cannot be discharged and system output can only come from...

Страница 17: ...7000W 20ms Input Voltage Limits Bypass L L 180 to 280V 240V nominal Input Frequency Range Bypass 45 to 54 9Hz 55 to 65 Hz AC OUTPUT TO GRID GRID SUPPORT Output Power Continuous 25 C 5000W Grid Sell C...

Страница 18: ...e connecting the 4 pin terminal block in the inverter s AUX GEN board Wiring the Current Sensor Make sure inverter s hardware version is 2 or above CTs cannot be installed with inverter hardware versi...

Страница 19: ...step 5 Remove the access panel and locate the emergency port Insert the 2 pin connector from the emergency button into the emergency port then skip to step 7 Remove the white 2 pin connector from the...

Страница 20: ...ing the button down pull the safety cover away Reset the emergency button Rotate button clockwise The button will pop back to the starting position Reset the safety cover Push the top section of the s...

Страница 21: ...trademarks of Darfon Electronics Corp All other trademarks are the property of the respective owners Manufactured by Darfon Electronics Corp 167 Shan ying Road Gueishan Taoyuan 333 Taiwan R O C Tel 88...

Отзывы: