I NS TA LL A TI ON  M A NU A L  

H 5 0 0 1   H Y BR I D   I NV E R T ER  

R E V . 4  

©20 2 2 D A R F ON  E LEC TR ON I CS  COR P.  

1 9

  |  PA G E  

APPENDIX D: EMERGENCY SHUTDOWN BUTTON [SOLD SEPARATELY] 

Wiring the Emergency Shutdown Button to the Inverter 

 

Turn off the system. 

 

Check the AUX GEN board version. The board will either be green or yellow. If it is yellow, skip to step 5. 

 

 

 

Remove the access panel and locate the emergency port. 

 

 

 

Insert the 2-pin connector from the emergency button into 
the emergency port, then skip to step 7. 

 

 

Remove the white 2-pin connector from the emergency 
button by disconnecting the terminal blocks. 

 

 

 

On the yellow AUX GEN board, connect the terminal block into RLY Input (pins 6 and 7). If a 7-pin terminal block is already 
there, remove the red and white wire from the 2-pin terminal block and insert it into pins 6 and 7. 

 

 

 

Test the emergency shutdown button. 

Содержание H5001

Страница 1: ...INSTALLATION MANUAL H5001 HYBRID INVERTER...

Страница 2: ...rs 8 Battery Charging Requirements 9 Communication Ports 9 Access Panel 10 TURNING THE SYSTEM ON OFF 11 Turning On the System 11 Turning Off the System 11 OPERATION AND DISPLAY PANEL 12 Display Overvi...

Страница 3: ...enance or cleaning or working on any circuits connected to the inverter Turning off controls will not reduce this risk Internal capacitors can remain charged for 5 minutes after disconnecting all sour...

Страница 4: ...UNCTION Piston Breakers For Over Current Protection of Grid L1 L2 Dip Switches For Firmware Update Jumpers For Firmware Update USB B For Computer Connection Communication Ports Power Switch Battery Br...

Страница 5: ...ution Degree rating The unit is for indoor applications only and must be mounted in a protected area that is dry free of excessive dust and has adequate air flow CAUTION The inverter is heavy 87lb 40k...

Страница 6: ...d 5 Time Of Use Low electricity cost Operate as Back up mode High electricity cost Operate as Residential mode 6 Time Of Use With Battery Feed In Low electricity cost Operate as Back up mode High elec...

Страница 7: ...se power surges that exceeds the inverter specifications When the grid is present the inverter can accept power surges up to 7 5kW for 30 seconds When the grid is absent the inverter can accept power...

Страница 8: ...ng or modifying any connections To prevent the risk of electric shock make sure the ground wire is properly earthed before operating this unit whether the grid is connected or not To reduce the risk o...

Страница 9: ...communication battery communication external display connection and parallel operation The ports are located inside the distribution box on the top bulkhead panel PORT FUNCTION RJ45 For External Displ...

Страница 10: ...r Over Current Protection There are three circuit breakers that protect the Grid path One circuit breaker is in the distribution box and is rated at 40A The piston breakers are for Grid L1 L2 and are...

Страница 11: ...e battery Refer to the battery s instruction manual Turn on the grid breaker if grid is connected Turn on the Power Switch Wait for system bootup and the fans to turn on plus 3 beeps Turn on the Load...

Страница 12: ...ction Exits setting mode Previous page previous item or decrease number ICON DESCRIPTION Represents the PV Array Represents the Battery Pack Represents the Utility Represents the Load Represents the H...

Страница 13: ...d use the key to set it When done press the key You will see a message stating the settings are being updated When you see Setting OK message press any key Manually restart the inverter using the Powe...

Страница 14: ...AC breakers must be sized for 40A or less and 2 all wiring must be sized for 40A or more The following diagram shows how the distribution box is electrically connected to the hybrid inverter NOTES Th...

Страница 15: ...If the error remains turn off the Utility and the inverter s Grid breaker Then measure the Grid and make sure the impedance of L1 L2 and N relative to ground and to each other should be an open circui...

Страница 16: ...the Grid or PV to charge the battery Warning code will change to 62 once the battery voltage is above 44V or the SOC is above 10 Note Battery cannot be discharged and system output can only come from...

Страница 17: ...7000W 20ms Input Voltage Limits Bypass L L 180 to 280V 240V nominal Input Frequency Range Bypass 45 to 54 9Hz 55 to 65 Hz AC OUTPUT TO GRID GRID SUPPORT Output Power Continuous 25 C 5000W Grid Sell C...

Страница 18: ...e connecting the 4 pin terminal block in the inverter s AUX GEN board Wiring the Current Sensor Make sure inverter s hardware version is 2 or above CTs cannot be installed with inverter hardware versi...

Страница 19: ...step 5 Remove the access panel and locate the emergency port Insert the 2 pin connector from the emergency button into the emergency port then skip to step 7 Remove the white 2 pin connector from the...

Страница 20: ...ing the button down pull the safety cover away Reset the emergency button Rotate button clockwise The button will pop back to the starting position Reset the safety cover Push the top section of the s...

Страница 21: ...trademarks of Darfon Electronics Corp All other trademarks are the property of the respective owners Manufactured by Darfon Electronics Corp 167 Shan ying Road Gueishan Taoyuan 333 Taiwan R O C Tel 88...