I NS TA LL A TI ON M A NU A L
H 5 0 0 1 H Y BR I D I NV E R T ER
R E V . 4
©20 2 2 D A R F ON E LEC TR ON I CS COR P.
5
| PA G E
Dead-Front Cover
Notes
The dead-front cover must be
removed when making or modifying
connections in the distribution box,
and reinstalled when connections
have been completed.
To remove the dead-front cover, use
the following steps.
Reverse the steps to reinstall the
dead-front cover.
Remove the screws from the dead-
front cover.
Pull off the dead-front cover.
Mounting the Inverter
Notes
The unit cannot be mounted on flammable construction materials.
Allow 20cm (8in) of clearance to the sides and 50cm (20in) to the top and bottom of the unit for
proper air circulation to dissipate heat.
The unit has an IP20 protection rating and a PD2 Pollution Degree rating. The unit is for indoor
applications only and must be mounted in a protected area that is dry, free of excessive dust and
has adequate air flow.
CAUTION. The inverter is heavy (87lb/40kg). Mounting should be handled by two people.
Do not place any additional weight onto the inverter.
Mounting Dimensions
Wall Types
Stud: The inverter will need to be mounted to the wall using Unistrut. The Unistrut must be secured
to two studs in the wall. There should be two rows of Unistrut installed: one for the backplate and
the other for the side brackets.
Solid: Use the backplate and mounting dimensions to mark for screw locations.
Mount the backplate onto the wall.
Install the brackets the inverter.
Hang the
inverter onto
the backplate.
Secure the brackets to the wall. Note: Screw can go into either top or bottom slot of the bracket.
197mm
(7.8in)
237mm
(9.3in)
394mm (15.5in)
475mm
(18.7in)
605mm
(23.8 in)
90mm
(3.5in)
30mm
(1.2in)
Содержание H5001