16
Description of the control board,
continued
Test points,
Silencio 800, 1000
and 1400
Here are the test points for the Silencio 800, 1000 and 1400:
Te
s
t point
Des
c
ription
Heat
er
Dampe
r
Internal fan
Compres
s
or
Conde
ns
e
r fa
n
LED
Duration
1
IDLE
Off
Closing
Stopped
Stopped
Stopped
Jingle
30 sec.
2
Heating
mode
On
Closing
700 RPM
Stopped
Stopped
Normal
90 sec.
3
Free
cooling
Off
Opening 1000 RPM
Stopped
1050 RPM
Normal
90 sec.
4
Active
cool
Off
Closing
1400 RPM
Running
1400 RPM
Normal
90 sec.
5
IDLE
Off
Closing
Stopped
Stopped
Stopped
Normal
30 sec.
Содержание Silencio 600