Fault finding guide,
continued
Fail
A fail is activated on one of the following events:
•
The heater is faulty – doesn’t use current. Loss of mains power
•
Fail on ambient air sensor – short or open circuit
•
Smoke alarm input activated
•
One of the external DC fans is stopped – no rotational pulses
•
The internal DC fan is stopped – no rotational pulses
•
Mains failure
Alarm
An alarm is activated on one of the following events:
•
Both the internal DC fans are stopped - no rotational pulses
•
Both the external DC fans are stopped - no rotational pulses
•
The compressor doesn’t draw current – this due to a dropout in the HP/LP pressure
switch, the winding protector or the compressor in general
•
Fail on the return air sensor – open or short circuited