15
018717 • Version
1.1 • 23.01.2007
Description of the control board,
continued
Signals of LED
The LED gives you different signals. The below table gives you a description of each
signal:
Part
Function
1 × Green LED
Supply
Lit as soon as the controller is powered up
3 × Yellow LED
Compressor
Lit when the active cooling is operating
Heat
Lit when the heater is operating
Link
Lit when (and 10 min. after) valid
communication is in progress
1 × Red LED
Fail
Lit in case of a detected failure, see details in
section “Fault finding guide”, page 71.
Test description
When activating the test button the unit starts the test program. The unit will run through
the different tests according to the below table.
The fail LED will operate normally indicating fail if and when detected.
If any fail is detected during the test, the LED will flash with a frequency of 1 Hz for
30 seconds after the test is done to indicate some fault were detected.
Test points,
Silencio 600
Here are the test points for the Silencio 600:
Te
s
t point
Des
c
ription
Heat
er
Dampe
r
Internal fan
Compres
s
or
Conde
ns
e
r fa
n
LED
Duration
1
IDLE
Off
Closing
Stopped
Stopped
Stopped
Jingle
30 sec.
2
Heating
mode
On
Closing
400 RPM
Stopped
Stopped
Normal
60 sec.
3
Free
cooling
Off
Opening 700 RPM
Stopped
450 RPM
Normal
60 sec.
4
Active
cool
Off
Closing
700 RPM
Running
700 RPM
Normal
60 sec.
5
IDLE
Off
Closing
Stopped
Stopped
Stopped
Normal
30 sec.
Continued overleaf
Содержание Silencio 600
Страница 1: ...Silencio Service manual EN No 018717 ver 1 1 23 01 2007...
Страница 76: ...76 Continued overleaf...
Страница 86: ...86 Accessories continued Wiring diagram page 6...