1. GENERAL
3
1.1 Introduction
The DanX type XWPS, XKS and XK equipment is designed for the use for ventilation,
humidity and temperature control in private and public swimming pool areas. The use of the
unit includes the required inspection and maintenance for these units, which is described in
the back of this manual.
Unloading, transportation, assembly, connecting of the DanX modules should only be
carried out by trained specialists
or by people supervised by authorized staff. It is the
responsibility of the fitter to read and understand this guide and other given information.
1.2 Foundation for the unit
The DanX unit must be installed in a location that meets the following requirements:
•
The supporting structure must be level, stable and vibration-free.
•
The supporting structure must be able to bear the weight of the unit.
•
The deflection of the substructure should be max. 1 mm/m.
•
For the connection of the condensate drain, it is necessary that the height between
condense outlet of the unit and the substructure is at least the required height for the
water
trap.
•
If the unit is mounted on a roof, the bearing ability of the roof and its support structure
must be examined.
1.3 Minimum distances
For the operation, maintenance and servicing of parts as heating coils, dampers and others
a minimum clearance between inspection side of the unit and the wall should be the width of
the unit. It is also recommended to have a minimum clearance of 600 mm between the wall
and the rear of the unit for service and installation purposes.
Model
W min [mm]
Model
W min [mm]
DanX 2/4
900
DanX 9/18
1800
DanX 3/6
900
DanX 12/24
2200
DanX 5/10
1400
DanX16/32
2200
DanX 7/14
1900