Installation
: Starting up
Starting up
Step Action
Illustration
1
Insert SD card into memory card
slot.
2
Switch power on.
Note:
The CC 3000 controller
is powered via the free cooling
unit.
3
The CC 3000 controller will now
start up with a short delay and
automatically install newest
firmware and run a GFX update.
Wait while the firmware is
installed. Do NOT switch off the
power or remove the SD card
during this process.
4
When the installation process is finished, the display will automatically open the
product configuration menu.
Choose and confirm your product. The controller will now read the corresponding
configuration.
5
Default language pack is English. You can choose another language in the language
setting menu. (Follow procedure in section “Language settings” on page 29)
6
Save your customized configuration to the SD card, if you want a backup or want to
copy it to other controllers.
• Go to menu item “Other settings” on page 30(see “Fig. 13” on page 23 for
menu overview)
→
setting option: “Backup”.
• The controller will now save a backup on the SD card.
(Backup file is named cc_cfg.txt, but can be renamed with max 8 characters)
7
Data log needed:
Leave SD card in the slot, if an operational data log is required. (See also section “Firm-
ware, datalog & communication” on page 33)
NO data log needed:
Remove SD card from the slot, if no data log is required. Settings are now stored in
onboard nonvolatile memory.
Step Action
1
Start a self test (automatic or manual) in order to see if the system is set up and con-
nected correctly. See how to run self test on page 26.
2
Go to HOME display and check that indoor/ outdoor temperature reading and set
point is correct.
• In case shelter temperature is below set point, indoor temperature sensor can
be heated by hand, to check that fan starts when temperature reach set point
• Be aware that if sensor temperature reach air conditioner set point and air
conditioner is started, it has a minimum runtime of 3 minutes.