Introduction

: About this manual

About this manual

This document is a technical user manual for the CC 3000 free cooling controller intended for 

trained personnel only.

 This manual uses the following abbreviations for ventilation terminologies.

Abb .

Description

GUI/ UI

Graphical User Interface / User Interface

NO/NC

Normally opened (NO) 
• 

a contact that does not flow current in its normal state. Switching it on will 

close the contact, causing it to allow current flow.

Normally closed (NC)
• 

a contact that does flow current in its normal state. Switching it on will open 

the contact and disconnect the flow.

NOC

Network Operation Center

SELV

Safety Extra Low Voltage

SNMP

Simple Network Management Protocol is an internet standard protocol for col-

lecting and organizing information about devices on IP networks and for modify-

ing that information to change device behaviour.

TCP/IP

Transmission Control Protocol/ Internet Protocol

TTL link Hardware interface based on the electrical properties of TTL (Transistor-Transistor 

Logic)

Following symbols are used in this manual in order to draw attention to danger risks and ad-

ditional information of high relevance.

Symbols used

Warning

Caution

WARNING

This symbol in connection with the word “Warning” warns of a risk 

involving severe injury.

Warning

Caution

CAUTION

This symbol in connection with the word “Caution” warns of a risk of 

minor or moderate injury and material damage.

!

NOTICE

In connection with this symbol you will find further tips and information 

concerning the use of the device.

Warning and caution symbols are described in the following way:

Type and source of hazard

 Further elaboration, if relevant.

•  Measures to avert danger or immediate measures if the risk occurs are described in this 

way

Copying of this service manual, or part of it, is forbidden without prior written permission 

from Dantherm.

Dantherm reserves the right to make changes and improvements to the product and the 

service manual at any time without prior notice or obligation.

This unit is designed for long term durability. When total lifetime ends, the unit should be 

recycled according to national rules and with high environmental protection considerations.

Target group

Abbreviations in 

this manual

Symbols in 
this manual

Warning

Caution

WARNING/

CAUTION

Copyright

Reservations

Recycling

Содержание CC 3000

Страница 1: ...CC 3000 controller SERVICE MANUAL en Rev 1 4 2019 W48 2...

Страница 2: ......

Страница 3: ...ng 12 Installation 13 Mounting of the unit 13 Configuration of output 14 Installation options air conditioner 15 Configuration of digital input NO NC 16 External Connections 17 Starting up 20 Operatio...

Страница 4: ...manual in order to draw attention to danger risks and ad ditional information of high relevance Symbols used Warning Caution WARNING This symbol in connection with the word Warning warns of a risk in...

Страница 5: ...y procedures Read the entire manual before using the controller Risk of damaging equipment and human injuries Digital inputs must be connected to potential free contacts only internal 12V pull up Do N...

Страница 6: ...ctive Restriction of hazardous substances and is manufactured in compliance with the following harmonized standards EN 60950 1 2006 Information technology equipment Safety Part 1 EN 61000 6 2 2019 Ele...

Страница 7: ...trol in enclo sures always attempting to minimize energy consumption The controller is able to operate following equipment simultaneously two free cooling units two motorized exhaust dampers TC damper...

Страница 8: ...tailed connecting specifications in the section External Connections on page 17 Flexibox 1 Flexibox 2 Damper 2 Damper 1 A C 1 A C 2 Alarm 1 5 Alarm 6 10 Heater 24V DC Aux Ethernet Digital 1 3 T Sensor...

Страница 9: ...emperature drops below set point for A C off Emergency operation is a special boost operation where all connected cooling units both free cooling and A C starts up at the same time until temperature d...

Страница 10: ...crease decrease fan speed gradually between Min C and Max C Fig 5 Free cooling unit starts when outdoor temperature is min 3 C colder than set point If out door temperature is closer to or above set p...

Страница 11: ...re is min 1 C colder than indoor tempera ture If outdoor temperature is closer to or above set point and cooling is needed A C unit will operate on its own Fig 7 The free cooling unit is not active On...

Страница 12: ...e be detected after unpacking of the device or should the delivery be incomplete contact your salesman in charge or specialised dealer without delay The scope of delivery includes Amount Description I...

Страница 13: ...der to inte grate cable trays 5 Lead the cables from the exter nal desired equipment through the wall mount and into the main casing 6 Click the main casing on the wall mount 7 Fix the main casing to...

Страница 14: ...7 8 Fig 9 Jumper 1 5 Config 1 Moving the jumpers make it possible to change the configuration of the corresponding outputs from normally opened NO to normally closed NC Jumper 6 8 Config 2 Removing t...

Страница 15: ...4 from 24V DC default to dry contact when connecting AC as illustrated in option 3 and 4 Option 3 CC 3000 must be set in energy save mode or standard mode when A C is connected DC 3500 Split Air condi...

Страница 16: ...your PC SD card reader 2 Open the txt file with the file name that match your product The txt file can be opened with wordpad 3 Go to system control configuration section and change line 57 58 59 to...

Страница 17: ...1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 Fig 10 This illustration shows the terminals to be used for connecting accessory to the digital input...

Страница 18: ...Mating type Anytek KD061050A000G Pin J 9 A C 1 J 4 A C 2 Cable type 1 24 V AC 100 mA Output can be configured as dry contact or 0 24 V DC output For 0 24 V DC output a jumper on PCB must be set see p...

Страница 19: ...nytek KD081050A000G Pin J 11 T sensor J 35 I2C Comm humidity sensor Cable type 1 Room temp sensor NTC type 3 3 V DC 0 5 mm2 2 GND SCL 3 Hotspot temperature sensor NTC type SDA 4 GND GND The terminal r...

Страница 20: ...menu item Other settings on page 30 see Fig 13 on page 23 for menu overview setting option Backup The controller will now save a backup on the SD card Backup file is named cc_cfg txt but can be renam...

Страница 21: ...1 2 on page 28 Besides the main operation mode there is a possibility to enable following override modes Humidity control Changes operation when humidity is too high see more on page 28 Night mode Ch...

Страница 22: ...the name of the selected menu item 4 List of settings Displays the list of settings which can be activated changed under the selected menu item 5 Exit save button The exit save button is placed at th...

Страница 23: ...m config Level Cooling set point Zone 2 Damper settings Heater set point Cooling mode Zone 2 Cooling mode Zone 1 Humidity control settings Alarm configuration Product configuration Other settings Netw...

Страница 24: ...door temperature Displays current indoor temperature C 3 Operation status Shows the current operation status In active Heating Free cooling Active cooling A C operation Alert 4 Outdoor temperature Dis...

Страница 25: ...emperature level 3 Digital input 1 Digital input 2 Humidity low low indoor humidity Digital input 3 Humidity high high indoor humidity Filter guard 1 Standard Filter flow 1 filter pressure level 1 ana...

Страница 26: ...ually 3 Note down the status of the different components 4 Set back to None normal mode when visual check has been completed List of components Dampers open Fans max RPM 75 duty cycle Dampers close He...

Страница 27: ...s P band 1 between min and midpoint 1 Midpoint 2 C Defines P band 2 between midpoint 2 and max Midpoint RPM Defines fan speed in of max speed Defines how the motorized damper is operated It Can be set...

Страница 28: ...free cooling set point Medium high energy consumption and fixed temperature set point 3 Energy save mode Free cooling starts up first and A C is only activated as backup Medium energy consump tion hi...

Страница 29: ...ntroller for the right product When SD card is inserted and controller is started up for the first time the controller will automatically open the product configuration menu Choose the right product f...

Страница 30: ...s Air conditioner lead lag function Dual zone Enables dual zone cooling configuration English Enables English display language Unit DgC F Switch between Celsius or Fahrenheit display units Backup uplo...

Страница 31: ...9 Temp high 2 High temperature 2 alarm Temp High 3 High temperature 3 alarm Humidity low Low humidity alarm Humidity high High humidity alarm 10 Filter flow 1 Pressure level 1 alarm Filter flow 2 Pres...

Страница 32: ...splay The interface is very intuitive and provides a good overview of the CC 3000 operational functions and settings The WEB interface can thus be used for easy configuration of most vital settings an...

Страница 33: ...is to be used with a standard USB to TTL cable Use TTL link for following purposes Reading out system status information Changing configuration and settings Override function to verify correct connect...

Страница 34: ...mples Download configuration file Tftp i ip address get cc_cfg txt Upload configuration file Tftp i ip address put cc_cfg txt Download log file from SD card Tftp i ip address get stat_log txt Upload f...

Страница 35: ...he system returns back to normal operation mode when the set time has passed see Menu overview on page 23 in order to navigate to occupied mode or see setting op tions in occupied mode on page 35 We r...

Страница 36: ...DC out NO NC Max 60V DC I2 C Communication interface for 3 3V DC I2 C components RH sensor pressure sensor Max wire length 1 5 m Temp sensors room hotspot NTC type NTCLE100E3272GB0 3x digital input Fo...

Страница 37: ...37 Appendix Schematics Schematics Fig 17 Connection diagram PCB en...

Страница 38: ...38 Appendix Enclosure dimensions Enclosure dimensions 205 215 82 5 105 158 1 82 5 80 6 2 105 125 4 158 1 138 34 60 26 Wall Bracket Rear Cover Fig 18...

Страница 39: ......

Страница 40: ...support dantherm com Dantherm can accept no responsibility for possible errors and changes en Der tages forbehold for trykfejl og ndringer da Irrt mer und nderungen vorbehalten de Dantherm n assume a...

Отзывы: