50
Electrical connections,
continued
Connections to
mains voltage
Mains voltage terminal points of 7,5 mm distance:
Terminals
Function
1/2 Mains
L/N
phase/neutral
3/4/5
Fresh air damper
open/close/N
6/7/8 Recirculation
damper
open/close/N
9/10
Burner
step 1, potential free exit
11/12
Burner
step 2, potential free exit
13/14
Supply fan L/N
potential free exit
15/16
Exhaust fan
potential free exit
(exhaust controlled by the control unit clock)
Low tension con-
nections
Low tension connections, external of 5 mm distance.
Connections may be made by 8-conductor telephone wire, max length 50 m
Terminals
Function
20/21
External fan, run
exhaust fan, receipt
(for manual start of the exhaust unit)
22/23
ON/OFF switch
ON/OFF check entry for overriding (forced
day operation)
24/25
Room temperature sensor -
26/27
Duct temperature sensor
-
28/29 Check
entry
constant day operation
13/14
Supply fan L/N
potential free exit
15/16
Exhaust fan
potential free exit
(exhaust controlled by the control unit
clock)
Connections to control unit:
Terminals
Function
51
LED
red (not used)
52 LED
yellow
53
C1 program timer
heat, supply
54
C2, program timer
damper, exhaust
55 OFF
unit
off
56
0-5 V set point signal
-
57
+ 24 V
-
58 GND
-