46062-0299 <90-00016>
P
AGE
57
DISP # can be any or all displays from number 1 through 64
(and GPP’s internal displays 65-73).
PNT # can be any or all points from point 1 through 64.
CTRL # can be any or all points from 1 through 64, up to two
points can be assigned to each alarm.
Input Example:
RESP ID 5 DISP 2 PNT 7 TO CTRL 2,6
Output Response:
There is no immediate response to this command; however,
when the alarm is set, control points 2 and 6 will be set.
R
EVISION
L
IST
Purpose:
Displays the firmware’s revision number.
Format:
REV
Remarks:
Status Monitors with the expanded memory option will have
X82-00283-0X firmware, those without will have X82-00300-0X.
Input Example:
REV
Output Response:
DANTEL COS POLLING STATUS MONITOR 1 meg
COPYRIGHT 1991
PART# X82-00283-0X
OK
Input Example:
REV
PRINTER SYNTAX