Manage operating envelope
R
Requirement
The operating envelope for VZH scroll
compressors is given in the figures below and
guarantees reliable operations of the compressor
for steady-state operation.
Moreover, the discharge gas temperature must
not exceed 135°C (275°F). Steady-state operation
envelope is valid for a suction superheat within
5K to 30K (9°F to 54°F) range.
Single envelope control
Pressure settings
R410A
Working range high side
bar(g)
psig
9.9-41.1
144-596
Working range low side
bar(g)
psig
1.8-16.6
26-241
Maximum high pressure safety switch setting*
bar(g)
psig
43.7
634
Minimum low pressure safety switch setting
bar(g)
psig
1.5
22
Minimum low pressure pump-down switch setting
bar(g)
psig
1.5 bar below nominal evap. pressure with
minimum of 1.8 bar(g)
22 psi below nominal evap. pressure with
minimum of 26psig
*Maximum allowable pressure on high pressure side according to PED regulation.
C
ondensing t
emper
atur
e (°C
)
C
ondensing t
emper
atur
e (°F)
Evaporating temperature (°C)
Evaporating temperature (°F)
VZH operating envelop - R410A(SH5K/9°F)
Voltage: 200-240V/380-480V/525-600V
-40
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
32
41
50
59
68
77
86
95
104
113
122
131
140
149
158
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
-40
-31
-22
-13
-4
5
14
23
32
41
50
59
68
77
86
2400-6000rpm
1800-6600rpm
4200-6000r
pm
1000-6600rpm
1.4
1.2
1.1
1.3
Note:
zone1.1/1.2/1.3: reliable running, compressor discharge temperature will not exceed 135°C (275°F) with suction
superheat within 5K to 30K (9°F to 54°F) range
zone 1.4: Restricted area, compressor discharge temperature may go beyond 135°C (275°F) depending on superheat
and speed. Operation in this area is allowed if discharge temperature is below 135°C (275°F).